Inspection Status: Passed
Inspection History: COT - RSPL - Rough Soil
| Date |
Description |
Inspector |
Results |
Comments |
| 03/08/2019 |
COT - RSPL - Rough Soil |
MHASSAN |
Approved |
Entered by CBELL1 - |
| 03/06/2019 |
COT - RSPL - Rough Soil |
TVALENCIA |
Denied |
Entered by CBELL1 - 1- Shall provide directional fittings for the lavatory and water closet in hallway.
2- Shall provide a vent for the master shower waste line.
3- Shall provide a minimum of two times the pipe size for the trap arm to the clothes washer.
4- Shall provide minimum of 18 inches of stand pipe for the clothes washer.
5- Shall provide a vent for the exterior sink.
6- Shall provide a water test on the entire sanitary system up to the top of vents thru roof. |