Permit: T18CM06686

Parcel: 116040970

Inspection Status: Passed

Inspection History: COT - RSPL - Rough Soil 

Date Description Inspector Results Comments
03/08/2019 COT - RSPL - Rough Soil  MHASSAN Approved Entered by CBELL1 -
03/06/2019 COT - RSPL - Rough Soil  TVALENCIA Denied Entered by CBELL1 - 1- Shall provide directional fittings for the lavatory and water closet in hallway. 2- Shall provide a vent for the master shower waste line. 3- Shall provide a minimum of two times the pipe size for the trap arm to the clothes washer. 4- Shall provide minimum of 18 inches of stand pipe for the clothes washer. 5- Shall provide a vent for the exterior sink. 6- Shall provide a water test on the entire sanitary system up to the top of vents thru roof.