Permit: T18CM06259

Parcel: 140200220


Addresses:

841 E BANTAM RD

Inspection Status: Not Ready

Inspection History: COT - HCBU - Preslab  

Date Description Inspector Results Comments
02/06/2024 COT - HCBU - Preslab   Not Ready 2/6/24: Preslab not ready
02/12/2024 COT - HCBU - Preslab   Re-inspection required 2/6/24: Preslab not ready
2/12/24: Called Carlos once arrived on site for access code and did not get an answer. Gate is locked no access to site.
2/12/24: detail 3/S1 calls out for dowels every 48" O.C with 8" embedment into new footings and existing footing, missing throughout, rebar supports are creating voids as reinforcements (large debris supporting rebar), footing F4 requires 24"x24" by 18" height.
02/13/2024 COT - HCBU - Preslab   Partial Pass 2/6/24: Preslab not ready
2/12/24: Called Carlos once arrived on site for access code and did not get an answer. Gate is locked no access to site.
2/12/24: detail 3/S1 calls out for dowels every 48" O.C with 8" embedment into new footings and existing footing, missing throughout, rebar supports are creating voids as reinforcements (large debris supporting rebar), footing F4 requires 24"x24" by 18" height.
2/13/24: reinforcement per plan in rooms 104,105,106,107,108,109 ok to pour in progress areas. Partial pass
03/15/2024 COT - HCBU - Preslab   Passed