Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T18CM05621
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2018 | ELECTRIC - UNDERGROUND | Approved | LAST OF THE UNDERGROUND, BASEBALL MULTIPURPUSE FIELD 9EA 2IN CONDUITS TO SERVICE SECTION. | |
| 09/24/2018 | ELECTRIC - UNDERGROUND | Partial Approval | POLES S3 TO S4 AND 1 AND 2 INCH CONDUIT OK TO BACKFILL | |
| 09/18/2018 | ELECTRIC - UNDERGROUND | Partial Approval | POLE B4 TO A4 TO #7 BOX , RETENTION BASIN WALL TO GATE 2" CONDUIT OK TO BACKFILL | |
| 09/13/2018 | ELECTRIC - UNDERGROUND | Partial Approval | POLE C-1 TO SERVICE YARD POLE B-3 TO POLE A-3 TO SERVICE YARD POLE L-2 TO SERVICE YARD OK TO BACK FILL ALL UNDERGROUND THAT HAS BEEN INSPECTED TO THIS POINT. |
|
| 09/05/2018 | ELECTRIC - UNDERGROUND | Partial Approval | ELECTRIC CONDUITS AT S1 - S2: 4 EACH CONDUITS 2"; 3 EACH CONDUITS 1". OK TO COVER PROGRRESS AREAS. | |
| 08/16/2018 | ELECTRIC - UNDERGROUND | Partial Approval | LIGHT POLES AT GL: A2 - S1; TRENCHES WITH 2" CONDUITS. OK TO COVER PROGRESS AREAS. | |
| 08/09/2018 | ELECTRIC - UNDERGROUND | Partial Approval | OK FROM LIGHT POLE B1 TO A2 |