Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T18CM05587
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2019 | FIRE - FINAL | Approved | ||
| 07/24/2019 | FIRE - FINAL | Partial Approval | Okay for occupancy Pending items prior to final approval: Need to order KNOX Box, KNOX FDC caps, KNOX Lock Fence to the west needs to be changed to a gate. |
|
| 07/23/2019 | FIRE - FINAL | Partial Approval | Need to order KNOX Box, KNOX FDC caps, KNOX Lock Tested system not active due to equipment being put in the data room and do not want a false activation. Okay for TCO to move in equipment. Fence to the west needs to be changed to a gate Need to finish replacing painted heads |
|
| 07/19/2019 | FIRE - FINAL | Partial Approval | Fence to the west needs to be changed to a gate as originally shown on the DP. It does not need to slide. Neet to correct the TIXE signs and add back labels where needed and two-sided where needed. Provide FACP sign, Riser Room Sign, Electrical and mechanical room signs. Need to order KNOX Box, KNOX FDC caps, KNOX Lock Still need to test the operation of the FM200 and the Pre-Action Need to test the generator time Need to verify the shut down of the duct smoke detectors. Pay re-inspection fees prior to calling back in |