Permit: T18CM05587

Parcel: 14029200A

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T18CM05587

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/13/2019 FIRE - FINAL Approved
07/24/2019 FIRE - FINAL Partial Approval Okay for occupancy
Pending items prior to final approval:
Need to order KNOX Box, KNOX FDC caps, KNOX Lock
Fence to the west needs to be changed to a gate.
07/23/2019 FIRE - FINAL Partial Approval Need to order KNOX Box, KNOX FDC caps, KNOX Lock
Tested system not active due to equipment being put in the data room and do not want a false activation. Okay for TCO to move in equipment.
Fence to the west needs to be changed to a gate
Need to finish replacing painted heads
07/19/2019 FIRE - FINAL Partial Approval Fence to the west needs to be changed to a gate as originally shown on the DP. It does not need to slide.
Neet to correct the TIXE signs and add back labels where needed and two-sided where needed.
Provide FACP sign, Riser Room Sign, Electrical and mechanical room signs.
Need to order KNOX Box, KNOX FDC caps, KNOX Lock
Still need to test the operation of the FM200 and the Pre-Action
Need to test the generator time
Need to verify the shut down of the duct smoke detectors.
Pay re-inspection fees prior to calling back in