Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T18CM05587
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2019 | BUILDING - FINAL | Approved | All other approvals are completed | |
| 07/23/2019 | BUILDING - FINAL | Not ready for Inspection | TCO status is dependent on fire departments approval. Please take care of fire departments corrections and recall this inspection. Also chlorination report still needs to be submitted. | |
| 07/23/2019 | BUILDING - FINAL | Not ready for Inspection | TCO OK for moving in equipment and furniture, this was the same TCO status given by the fire department. Also chlorination report still needs to be submitted | |
| 07/19/2019 | BUILDING - FINAL | Partial Approval | OK for TCO for operations pending fire departments approval. For a full CO, complete exterior lighting on west side of building. Finish closing any open junction boxes. Exit sign needed in IT area (where the exit or path of egress travel is not immediately visible to the occupants, exit signs are needed 1011.1 IBC). Need special inspection reports submitted. Need required forms and reports for a C of O submitted. Need test and balance and chlorination report submitted. |