Permit: T18CM05587

Parcel: 14029200A

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T18CM05587

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/14/2019 BUILDING - FINAL Approved All other approvals are completed
07/23/2019 BUILDING - FINAL Not ready for Inspection TCO status is dependent on fire departments approval. Please take care of fire departments corrections and recall this inspection. Also chlorination report still needs to be submitted.
07/23/2019 BUILDING - FINAL Not ready for Inspection TCO OK for moving in equipment and furniture, this was the same TCO status given by the fire department. Also chlorination report still needs to be submitted
07/19/2019 BUILDING - FINAL Partial Approval OK for TCO for operations pending fire departments approval. For a full CO, complete exterior lighting on west side of building. Finish closing any open junction boxes. Exit sign needed in IT area (where the exit or path of egress travel is not immediately visible to the occupants, exit signs are needed 1011.1 IBC). Need special inspection reports submitted. Need required forms and reports for a C of O submitted. Need test and balance and chlorination report submitted.