Permit: T18CM04589

Parcel: 14043013B

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T18CM04589

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/23/2019 FIRE - ALARM FINAL Approved
08/16/2019 FIRE - ALARM FINAL Partial Approval One horn strobe needs to be synchronized
Power supplies and FACP need to have dedicated primary perminanent power not tem power
Need to label the power supplies and FACP with disconnectting means
Need to install the graphic annunciator
Need to put on the network to verify signals
Need asbuilt fire alarm plans
Need to test water flows, tampers, smokes and duct detectors