Permit: T18CM04589

Parcel: 14043013B

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T18CM04589

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/23/2019 FIRE SPKLR - FINAL Approved
08/16/2019 FIRE SPKLR - FINAL Partial Approval Completed the fire sprinkler 200 psi for the last riser. Need to relocate the PIV, Double back flow preventer and the FDC to outside of the new fence that they will be adding. Fire pump room needs a "test header" sign
08/15/2019 FIRE SPKLR - FINAL Partial Approval pump test approved
08/13/2019 FIRE SPKLR - FINAL Partial Approval Pump test approved pending final paperwork.
06/18/2019 FIRE SPKLR - FINAL Partial Approval Approved the OH Hydro. Need to add heads under all duct and transfer over 48". Do not need to hydro system for additional heads. Western States Permit # T19FC00144