Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T18CM04589
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/23/2019 | FIRE SPKLR - FINAL | Approved | ||
08/16/2019 | FIRE SPKLR - FINAL | Partial Approval | Completed the fire sprinkler 200 psi for the last riser. Need to relocate the PIV, Double back flow preventer and the FDC to outside of the new fence that they will be adding. Fire pump room needs a "test header" sign | |
08/15/2019 | FIRE SPKLR - FINAL | Partial Approval | pump test approved | |
08/13/2019 | FIRE SPKLR - FINAL | Partial Approval | Pump test approved pending final paperwork. | |
06/18/2019 | FIRE SPKLR - FINAL | Partial Approval | Approved the OH Hydro. Need to add heads under all duct and transfer over 48". Do not need to hydro system for additional heads. Western States Permit # T19FC00144 |