Permit: T18CM04555

Parcel: 14043013B

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T18CM04555

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2019 PLUMBING - YARD WTR LINE/TEST Approved 8 inch waterline fire and 2 inch potable water complete all tests
02/21/2019 PLUMBING - YARD WTR LINE/TEST Partial Approval Water service at north side of building two 2 inch yard waterlines (1 irrigation & 1 domestic) OK to cover.
02/20/2019 PLUMBING - YARD WTR LINE/TEST Cancelled canceled and rescheduled for tomorrow
01/16/2019 PLUMBING - YARD WTR LINE/TEST Partial Approval Completion of 8” fire line loop 200 lb test
01/14/2019 PLUMBING - YARD WTR LINE/TEST Partial Approval Laterals to be tested a later date see highlighted CU.UW1 plan
01/11/2019 PLUMBING - YARD WTR LINE/TEST Partial Approval South 8 inch Waterline Loop terminated to valve to be tested a later date
01/10/2019 PLUMBING - YARD WTR LINE/TEST Partial Approval 8 inch Waterline Loop South 180 feet to be tested at a later date
see highlighted CU1.UW1 plan
01/09/2019 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection work now complete enough to inspect
01/03/2019 PLUMBING - YARD WTR LINE/TEST Partial Approval After hours APA account $165.00
200 lb test 8" waterline at north loop GL 11 from A-N only
12/28/2018 PLUMBING - YARD WTR LINE/TEST Partial Approval 8 inch Waterline Loop NE. corner 60 feet to be tested a later date
see highlighted CU1.UW1 plan
12/27/2018 PLUMBING - YARD WTR LINE/TEST Partial Approval 8 inch Waterline Loop 60 feet to be tested it at a later date see highlighted CU1.UW1 plan
12/26/2018 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection Work not complete enough to inspect
12/20/2018 PLUMBING - YARD WTR LINE/TEST Partial Approval 8 inch Waterline Loop to be tested at later date see highlighted CUW.UW1 plan south west corner 110 foot of line
12/19/2018 PLUMBING - YARD WTR LINE/TEST Partial Approval final tap and sleeve southeast corner see highlighted plan CU 1.UW1 200 pound test
12/18/2018 PLUMBING - YARD WTR LINE/TEST Partial Approval 8 inch Waterline Loop West to be tested @ later date
Tap and sleeve 200 lb test
See highlighted see CU1.UW1 plan
12/17/2018 PLUMBING - YARD WTR LINE/TEST Partial Approval Tap and sleeves sw corner and ne corner of building 100 lb test. See highlighted cu1.uw1 plan
12/14/2018 PLUMBING - YARD WTR LINE/TEST Partial Approval 8" water line loop
See highlighted cu1.uw1 plan
To be tested at a later date