Permit: T18CM04555

Parcel: 14043013B

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
07/30/2019 ELECTRIC - UFER Approved
05/23/2019 ELECTRIC - UFER Denied Provide proper clearance steel from soil 4 pole bases north access road.
05/15/2019 ELECTRIC - UFER Partial Approval Completion of grounding loop main building only
05/09/2019 ELECTRIC - UFER Partial Approval UFER ground at structural steel southeast corner ok to cover.
UFER ground for chillers OK to cover.
05/07/2019 ELECTRIC - UFER Partial Approval 6 pole bases north parking lot only
05/06/2019 ELECTRIC - UFER Partial Approval completion of column grounding except two columns at West mechanical yard
Completion of ground ring except tie in at south west corner of building
04/11/2019 ELECTRIC - UFER Partial Approval Grounding a tank pads between grid lines G -H on Gridline 1
Grounding at three switchgear and vaults with ground rods GL 1.5 from H-J
04/01/2019 ELECTRIC - UFER Partial Approval Ground ring at column GL 1 from G-H
03/26/2019 ELECTRIC - UFER Partial Approval Ground ring GL 1 from D-E only
03/25/2019 ELECTRIC - UFER Partial Approval Column line A-E GL 2 and A-C GL 1 with ground rods
02/21/2019 ELECTRIC - UFER Partial Approval grid line N to K grounding ok to cover.
02/06/2019 ELECTRIC - UFER Partial Approval Grounding unless side of building OK to cover
02/01/2019 ELECTRIC - UFER Partial Approval Ground ring at column N/9 through L /10.5