Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2018 | FIRE - FINAL | Approved | ||
| 05/25/2018 | FIRE - FINAL | Partial Approval | Needs the following: 1) Annual fire sprinkler inspection report. 2) 5yr internal check valve inspection report. 3) Annual fire alarm inspection report. 4) Update knox keys, riser room and main entry. 5) Install and test EM lights/exit signs. 6) two sprink heads <6' apart in large room, south side. 7) Need to verify installatiion and test access controlled exit doors. 8) Post address on bldg. Min 12" numbers. |