Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T18CM00845

Parcel: 11304127A

Inspection Status: Denied

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
06/26/2019 PLUMBING - INTERMEDIATE Denied 1- Shall provide a Mission Specialty coupling on the 11/2 vertical lavatory vent.
2- Shall locate the horizontal vent for the Tubs 6 inches above the flood level rim of the fixture.
3- Re test the system.
06/26/2019 PLUMBING - INTERMEDIATE Approved
06/25/2019 PLUMBING - INTERMEDIATE Not ready for Inspection 1- Contractor called and cancelled the inspection request.
06/24/2019 PLUMBING - INTERMEDIATE Denied 1- Shall install the soil revent San Tees upside down for condensate drainage.
2- Shall complete the kitchen sink waste.
3- Shall provide a double fixture fitting for the back to back lavatory waste trap arms when the trap arms are less than 18 inches.
4- Re test the DWV system.
06/21/2019 PLUMBING - INTERMEDIATE Cancelled Canceled by contractor
06/20/2019 PLUMBING - INTERMEDIATE Denied no tests
06/19/2019 PLUMBING - INTERMEDIATE Not ready for Inspection Contractor cancelled.