Permit: T17FC00968

Parcel: 14043013B

Inspection Status: Passed

Inspection History: FCON – OH Piping & Hydro

Date Description Inspector Results Comments
04/19/2018 FCON – OH Piping & Hydro JPEELDAVIS Approved Entered by JPEELDA1 - All system areas 210 psi. Make sure that the duct work once wrapped is under the 48". If the wrapping exceeds the 48" you will need to add a head for proper coverage.