Permit: T17FC00793

Parcel: 11720015A


Addresses:

111 S CHURCH AV


Inspection Status: Approved

Inspection History: FIRE PUMP - FINAL

Permit Number - T17FC00793

Inspection Description - FIRE PUMP - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/15/2018 FIRE PUMP - FINAL Approved
10/29/2018 FIRE PUMP - FINAL Partial Approval Started the pump and control head. Performed the churn and flow test. They still need to install the Jockey pump so that we can test that for proper operation. Tested powerloss, phase reversal, pump running and all control valves with the fire alarm and monitoring as well.