Inspection Status: Approved
Inspection History: FIRE PUMP - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/15/2018 |
FIRE PUMP - FINAL |
|
Approved |
|
| 10/29/2018 |
FIRE PUMP - FINAL |
|
Partial Approval |
Started the pump and control head. Performed the churn and flow test. They still need to install the Jockey pump so that we can test that for proper operation. Tested powerloss, phase reversal, pump running and all control valves with the fire alarm and monitoring as well. |