12/13/2018 | FIRE SPKLR - FINAL | Approved | ||
12/04/2018 | FIRE SPKLR - FINAL | Partial Approval | All floors complete for Partial. Floors 1-3 all items are ok. 4-7 the notes are as follows: 7th floor north stairwell waterflow was 31 seconds 6th floor north stairwell waterflow was 31 seconds 5th floor north stairwell waterflow was 33 seconds 4th floor north stairwell waterflow was 32 seconds Floors 4-7 stairwell control valves and inspector test need to have proper signage Room 412 front entry escutcheon is painted Room 411 bedroom sidewall painted/drywall Room 411 closet head is painted Room 411 kicthen sidewall by fridge painted Room 410 closet by bedrooms in the hallway painted/drywall Room 410 back bedroom sidewall head painted Room 410 back closet esuctheon painted Room 402 closet escutcheon painted Room 404 hall closet escutcheon painted Room 404 bedroom escutcheon painted Room 405 linen closet painted/drywall Room 405 bathroom closet escutcheon painted/drywall Room 405 bedroom soffit escuctcheon painted Room 405 bedroom master closte escutcheon painted/drywall Room 408 bathroom escutcheon is painted Room 513 front entry ecutcheon is painted Room 513 bedroom sidewall and clost escutcheon are painted Room 513 bathroom escutcheon is painted Room 511 bathroom escutcheon is painted Room 510 hall clost head needs to be raised 5th floor elevator lobby left side sidewall is painted Room 502 pantry escutcheon dry wall Room 503 bathroom escutchion drywall Room 505 pantry escutcheon paint/drywall Room 505 bathroom closet needs to have the head raised Room 506 linen closet escutcheon has paint/drywall Room 507 bathroom head and closet head are painted Room 509 bathroom closet ecutcheon pained/drywall Room 508 bathroom closet esuctcheon painted dry wall Room 613 bathroom escutcheon needs to be raised Room 612 front entry missing the escutcheon and the head has dry wall on it Room 612 bathroom escutcheon has dry wall on it Room 612 hall back closet os missing the head Room 612 bedroom head by the fan has drywall on it Room 611 bathroom closet close the gap between escutcheon and the ceiling Room 611 living room sidewall is painted/drywall missing escutcheon and pushed back into the wall Room 611 back bedroom sidewall is painted Trash room 6th floor is taped 6th floor left side of the elevator lobby is painted 6th Floor maintenance room has taped heads Room 601 linen closet was locked no access need to check at final Room 601 bathroom head has drywall Room 602 back livingroom sidewall is painted Room 603 bathroom escutcheon has drywall Room 603 bedroom sidewall is painted Room 605 back livingroom sidewall is painted Room 605 entry by bathroom head has drywall Room 604 back livingroom sidewall has drywall Room 604 bedroom sidewall has drywall Room 607 linen closet esuctcheon has drywall Room 606 back living room has head with drywall Room 606 bathroom head is still capped Room 606 closet head is still capped in the bedroom Room 609 kicthen sidewall is painted Room 609 living room sidewall has drywall' Room 609 bathroom closet is capped Room 609 bedroom entry is mising the escutcheon Room 609 bedroom sidewall is painted Room 608 bathroom closet head is capped Room 608 bedroom sidewall has drywall on it Room 608 kitchen sidewall has drywall on it Room 608 livingroom sidewall is painted 7th floor MPR kitchen closet has the head capped 7th floor left elevator lobby escuctheon has paint on it Room 701 kitchen escutcheon has drywall Room 703 pantry escutcheon is painted Room 703 linen closet escutcheon is painted Room 703 bathroom closet escutcheon is painted Room 703 bedroom and closet heads are capped Room 704 pantry escutcheon is painted Room 704 linen escutcheon is painted Room 707 pantry escutcheon is painted Room 707 bathroom closet escutcheon is painted Room 707 bedroom and closet heads are capped |
|
11/15/2018 | FIRE SPKLR - FINAL | Partial Approval | Fire sprinkler final for the 1st, 2nd and 3rd floor only. Added the additional fees. |