Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T17FC00280
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2017 | FIRE - ALARM FINAL | Approved | Per JV to verify fire phones installed and fire curtain complete. | |
08/22/2017 | FIRE - ALARM FINAL | Partial Approval | 3rd floor inspection only. Floors 3,4,5 all approved. Need the following to final permit. 1) Need to test flow switch 4th floor once repaired. 2) As builts 3) FF phone volume too low. 4) Add strobe, ADA room, bathroom. |
|
07/25/2017 | FIRE - ALARM FINAL | Partial Approval | PA 4th floor inspection only: 1) need to test NE flow and tamper (janitor closet). They are being replaced. 2) Need FF phones installed/tested. 3) Need to test talkaphones. 4) Dampers on 4th and 5th tested (they worked/approved). 5) Additional reinspection fee added. Must be paid prior to next inspection. 6) Some items from 5th floor still need approval. See items from previous list, #1, 3, 5. APPROVED TO OBTAIN TCO FOR FULL OCCUPANCY ON 4TH FLOOR. |
|
06/30/2017 | FIRE - ALARM FINAL | Partial Approval | Inspected 5th floor only. This is a PA for 5th floor only. Still need the following for a full approval on 5th floor. 1) Install talkaphones. 2) Need to verify alarm on floor below. 3) Need FF phones installed. 4) Need to install/download low freq. message and field verify. 5) Label all breakers and lockout. 6) Additional reinspection fees will be added accordingly. |