Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/27/2017 |
FIRE - ALARM FINAL |
|
Approved |
|
| 06/13/2017 |
FIRE - ALARM FINAL |
|
Denied |
Hornstrobes need to be synchronized, add weatherproof strobes to the 2 walk-in coolers, add strobe back door area by freezer 17, add horn strobe back accessway, add horn strobe storage room 1, add strobe storage room 2, shut down the music, re-test the ansul system, add red lock out to breaker, confirm monitoring |