Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2017 | INSP - INITIAL CODE ENFORCMENT | Approved | EXTERIOR INSPECTION: THERE ARE TWO MAIN DISCONNECTS ON THE BUILDING. THE 30 AMP IS FOR THE 607 W SIMMONS RD ADDRESS WHICH IS OCCUPIED, THE OTHER DISCONNECT IS FOR THE BOAT HOUSE AND THE 611 ADDRESS CURRENTLY A VACANT BUILDING. THE MAIN DISCONNECT FOR THE 607 W SIMMONS RD HAS ONE NON METALLIC SHEATHED CABLE PROVIDING POWER TO THE HOME. THE INSTALL OF THE CABLE IS AN UNAPPROVED WIRING METHOD. THERE IS NO GROUNDING SYSTEM. THERE ARE UNUSED OPENINGS ON THE EQUIPMENT. UNIT 611 W SIMMONS RD HAS AN INTERIOR PANEL WITH 4 CIRCUIT BREAKER. THIS IS NEW EQUIPMENT. THERE ARE MULTIPLE WALL OUTLET WITH DAMAGED, BURNT RECEPTACLES. THE BUILDING HAS NO MAIN DISCONNECT. NO GROUNDING SYSTEM. THERE ARE ELECTRICAL CODE VIOLATIONS WITH THE OUTDOOR ELECTRICAL EQUIPMENT. |
|
| 11/06/2017 | INSP - INITIAL CODE ENFORCMENT | Approved | Stiil Tenants will not allow interior inspection, ask if they have any issues with unit, both tenants in both unit say no issues with unit, will need to address exterior violations for now. have been trying to make contact with owner but goes stright to voice mail. | |
| 11/02/2017 | INSP - INITIAL CODE ENFORCMENT | Approved | Met with the tenants of the property and inspected on Monday. RV. |