Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T17DV04190

Parcel: 120070970


Addresses:

150 W LINCOLN ST

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
09/01/2017 INSP - INITIAL CODE ENFORCMENT Approved EMERGENCY CALL OUT BY TPD: TRANSIENT LIVING WITH OUT POWER IN THE FRONT SHED AND UNITS 1 AND 2. MAIN DISCONNECTS HAVE MULTIPLE CODE VIOLATIONS, TEP WAS CALLED OUT DUE TO TAMPERING WITH THE ELECTRICAL SYSTEM. TEP DID REMOVE METER FROM UNIT 1 AND WAS UNABLE TO PULL METER OFF CENTER PANEL LABELED UNIT 2 DUE TO TAMPERING, FEEDERS WERE CUT OFF AT THE SERVICE DROP. PANEL LABELED UNIT 3 HAS CONDUCT OPEN AND CUT EXPOSED CONDUCTORS.. THE ENTIRE SERVICE HAS NO GROUNDING ELECTRODE SYSTEM AND UNUSED OPENINGS. SEVERE TAMPERING WITH UNITS 1 DOWN STREAM PANELS MISSING CONDUCTORS TO THE UNIT, FEEDERS EXPOSED AND DISCONNECTED, USED OPENINGS. INTERIOR DAMAGE TO UNIT 1 DRYWALL CEILINGS AND WALLS, MISSING HARDWARE DOOR LOCKS TO TWO EXIT DOORS. BEDROLLS AND FOOD CONTAINERS IN EVERY ROOM, UN DISPOSED FECES IN BATHROOM.
UNIT 2 TENANTS HAD A GENERATOR WITH EXTENSION CORDS, TENANTS STATED THEY DO USE THE GENERATOR TO BACK FEED THE UNIT. THE INTERIOR HAS MULTIPLE EXTENSION CORDS BEING USED FROM THE GENERATOR.
UNITS 1, 2 AND THE SHED WERE SECURED BY PINNING OR SCREWING AND BOARDING. ALL ABOVE UNITS AND THE SHED WAS CONDEMNED. PLACARDS POSTED,, CLOSE CASE
09/01/2017 INSP - INITIAL CODE ENFORCMENT Approved ON SITE INSPECTION TPD EVENT NUMBER 1709010169 OFFICER GONZALES