Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T17DV00060

Parcel: 12806072E


Addresses:

1065 S CRAYCROFT RD

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
01/07/2017 INSP - INITIAL CODE ENFORCMENT Approved EMERGENCY CALL OUT BY TFD: HOOD FIRE AT KFC, TFD STATED THAT THERE WAS FIRE IN AND ABOVE THE HOOD AROUND THE EXHAUST DUCT. THE HOOD IS ESTIMATE 16 FEET LONG WITH ONE 16" X16" EXHAUST DUCT, WHILE THE DROPPED DOWN CEILING TILES WERE REMOVED BY TFD, I SAW A CUT OUT IN THE CEILING FOR ANOTHER EXHAUST DUCT WHICH WAS COVERED UP. THE SIDE OF THE HOOD WHICH DOESN'T HAVE AN EXHAUST DUCT HAS (2) HOT HOLDING UNITS (OVEN WARMERS) UNDERNEATH. IM CONCERNED ABOUT ONLY ONE DUCT FOR THE ENTIRE HOOD SYSTEM. THE FRYERS WERE LEFT ON. THERE IS MC CABLE ABOVE THE HOOD AND AN OUTLET WITH A DUPLEX RECEPTACLE SATURATED WITH OIL BEHIND THE FRYERS. THE ANSUL SYSTEM DID NOT DEPLOY. THERE IS NO STRUCTURAL DAMAGE TO THE BUILDING.
SWG DID SHUT THE GAS OFF. TEP DID LOCK OUT THE POWER.
THERE IS DAMAGE TO THE CEILING TILES. THE 4 INTERIOR PANELS HAVE CODE VIOLATIONS, CIRCUIT BREAKERS WHICH ARE UNREADABL, DAMAGED AND NO LABELING ON THE PANELS. ONE CIRCUIT BREAKER HAS A HOMEMADE HANDLE TIE. THE FRONT DOOR TO THE BUILDING WERE FORCED OPEN, THE MANAGER DID SECURED THE BUILDING, THE BUILDING WAS CONDEMNED, PERMITS REQUIRED FOR REPAIRS TO THE HOOD SYSTEM, FIRE SYSTEM, ELECTRICAL AND GAS,
SCHEDULE A 30 DAYS INSPECTION FOR THE AREA INSPECTOR