Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2017 | INSP - INITIAL CODE ENFORCMENT | Approved | THERE WAS DAMAGE TO THE WALL SIDING IN THE PATIO AREA CAUSE BY A FIRE FROM ADJACENT PROPERTY ADDRESSED AT 1347 E NEVADA. TUCSON FIRE DEPATMENT DID REMOVE THE DAMAGED WALL SIDING AND ALSO CUT THE ROOF SHEATHING. THE ELECTRICAL VIOLATIONS ON THE DOWNSTREAM PANEL ARE NOT AS A RESULT OF THE FIRE BUT AS FOLLOWS: THERE ARE MULTIPLE CONDUCTOR TERMINATIONS IN THE SAME TERMINAL LUG AT THE CIRCUIT BREAKER, NUETRAL BAR AND THE MAIN BUS. GROUNDS AND NEUTRALS ARE NOT SEPARATED. THE DEAD FRONT NOT INSTALLED AND HAS NO LABELING. MAIN PANEL HAS NO LABELING.FOLLOW UP DUE IN 30 DAYS FOR INSPECTOR VIDAL ALL DOCS AND PICS IN SIRE |