Permit: T17CM09357

Parcel: 13705494G


Addresses:

4605 S LANDING WY

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
08/10/2018 FIRE - ALARM FINAL Approved
08/07/2018 FIRE - ALARM FINAL Partial Approval Need to test the following zones. They did not report.
CO2 high
CO2 power loss (primary and secondary)
smoke alarm
RTU's
FACP power loss
Hood
Possibly some others. Should conduct an entire fire alarm final to verify all signals.