Permit: T17CM09232

Parcel: 117142140

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/18/2019 PLUMBING - INTERMEDIATE Approved
04/24/2019 PLUMBING - INTERMEDIATE Partial Approval Pending verification of ADA shower diverter location
04/23/2019 PLUMBING - INTERMEDIATE Not ready for Inspection work now complete comply with previous
04/22/2019 PLUMBING - INTERMEDIATE Denied 1- Shall provide a vent for all of the second floor shower drains.
2- Shall provide 18 inches of frontal clearance for 1st floor 3 inch clean out.
3- Retest the system.
04/19/2019 PLUMBING - INTERMEDIATE Partial Approval PVC piping under test OK
02/12/2019 PLUMBING - INTERMEDIATE Not ready for Inspection sewer HCS OK