Permit: T17CM08953

Parcel: 11620134B


Addresses:

875 W CUSHING ST


Inspection Status: Passed

Inspection History: COT - FCON - Fire - Final

Permit Number - T17CM08953

Inspection Description - COT - FCON - Fire - Final

Inspection Status - Passed

Date Description Inspector Results Comments
09/17/2019 COT - FCON - Fire - Final JPEELDAVIS Approved Entered by JPEELDA1 - Tested the emergency responder radio coverage. New south exposure address approved. Ok for COFO.
04/17/2019 COT - FCON - Fire - Final jvincent Partial Approval Entered by JVINCEN1 - 1. Needs BDA installed/approved/finaled. 2. Lower FDC's. Max 48".
04/16/2019 COT - FCON - Fire - Final JVINCENT Partial Approval Entered by AVAUGHN1 - TCO TO INCLUDE 3RD FLOOR PATIO AND FITNESS CENTER
03/12/2019 COT - FCON - Fire - Final JPEELDAVIS Partial Approval Entered by JPEELDA1 - Emergency Responder Radio Coverage test failed 2nd and 3rd floor. Need to install BDA prior to COFO.
03/04/2019 COT - FCON - Fire - Final JPEELDAVIS Partial Approval Entered by JPEELDA1 - Tested the emergency and exit lighting. Front entry and west side of the first floor do not have emergency lights installed. Asked that they provide photometrics showing that they meet the 1 candella and or 11 lux in that area and or add emergency and exit lights. Will need to test this again for COFO.
03/01/2019 COT - FCON - Fire - Final jvincent Partial Approval Entered by MROSS2 - TCO APPROVED FOR FULL OCCUPANCY. FULL FINAL/CofO PENDING LIST OF ITEMS FROM JPD. TCO DOES NOT INCLUDE FITNESS CENTER. ADDRESS NUMBERS/STREET NAME REQUIREMENT TO BE ADDRESSED BY FIRE CODE OFFICIAL.
02/28/2019 COT - FCON - Fire - Final JPEELDAVIS Partial Approval Entered by JPEELDA1 - Per conversation with the owner of CAT the movie projector does not produce sound and they use a sunglass type technology only so the shut down with the FACP will not be required.
02/28/2019 COT - FCON - Fire - Final JPEELDAVIS Partial Approval Entered by JPEELDA1 - 1) Need to test for emergency responder radio signal and provide documentation to TFD prior to COFO 2) Need KNOX caps on the FDC 3) Need to place the brass caps on the standpipes 4) Address on the Avenida De Convento Side needs to be 875 W Cushing not just 875 5) Install a KNOX box at doors and the chiller yard 6) Sign for the chiller yard 7) Stair 1 needs to have a lock and or handle so that we can gain access 8) Front entry by Stair 1 need to confirm that they have 11 lux or 1 candle foot and or provide bug lights for emergency egress 9) Move the exit sign at the elevator lobby 1st floor so that it does not lead you into a wall 10) Fire alarm needs to shut down the movie room projector 11) Install door and hardware at the shared lab 12) If there are ADA showers you will need to add notification devices in those stalls. 13) Add chevron to the south wall eit sign by lobby area 14) Need to check with the locks on the front door 15) Need to have the fire sprinkler final on the 3rd floor complete
01/25/2019 COT - FCON - Fire - Final gsereno1 Partial Approval Entered by GSERENO1 - Discussion on Exit sign placement first floor. Re-inspection fee added
01/17/2019 COT - FCON - Fire - Final CBASALDUA Partial Approval Entered by CBASALD1 - 1. Fire extinguisher placement approved for 2nd Floor. 2. Fire Sprinklers approved on 2nd Floor. 3. EM lights and exit lighting approved on 2nd Floor. 4. Ok for TCO to furnish 2nd Floor.
01/17/2019 COT - FCON - Fire - Final CBASALDUA Partial Approval Entered by AVAUGHN1 - TCO FOR 2ND FLOOR
12/19/2018 COT - FCON - Fire - Final JPEELDAVIS Partial Approval Entered by JPEELDA1 - Checked the emergency and exit lights 3rd floor - approved Checked the fire extinguisher placement 3rd floor - approved Tested the fire alarm and the fire sprinkler for the 3rd floor. OK for TCO to furnish the 3rd floor