Permit: T17CM08953

Parcel: 11620134B


Addresses:

875 W CUSHING ST


Inspection Status: Passed

Inspection History: COT - HCME - Hydronic Piping 

Permit Number - T17CM08953

Inspection Description - COT - HCME - Hydronic Piping 

Inspection Status - Passed

Date Description Inspector Results Comments
02/28/2019 COT - HCME - Hydronic Piping  RCAMACHO Approved Entered by CBELL1 -
09/19/2018 COT - HCME - Hydronic Piping  RCAMACHO Partial Approval Entered by CMURPHY1 - Chill water 6 inch line 80 lb PSI test okay to insulate refrigerant lines 750 lb PSI test 3rd floor 2nd floor and shaft only
09/14/2018 COT - HCME - Hydronic Piping  RCAMACHO Not ready for Inspection Entered by CMURPHY1 - Tes call center room 3597 Tes Tech Lab room 3096 Tes remote Moon Room 3095 Tes War Room 3094 open offices rooms 3091 and 3093 Mech yard only No test Shaft 1 condensate line only Mechanical shaft number 1 and 3 complete shaft number 2 except exhaust all hard duct GL 10 to 14 from A to C okay to insulate
02/22/2018 COT - HCME - Hydronic Piping  mramber1 Partial Approval Entered by MRAMBER1 - 100 psi test ok at S.E. corner, provide hydrostatic test when system complete