Inspection History Details
Inspection Status: Passed
Inspection History: COT - HCEL - Electrical Intermediate
Permit Number - T17CM08953
Inspection Description - COT - HCEL - Electrical Intermediate
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/28/2019 | COT - HCEL - Electrical Intermediate | RCAMACHO | Approved | Entered by CBELL1 - |
02/06/2019 | COT - HCEL - Electrical Intermediate | TVALENCIA | Partial Approval | Entered by CBELL1 - 1- MC cables and metal boxes are okay in rooms 1085 thru 1090 only. |
01/25/2019 | COT - HCEL - Electrical Intermediate | DQUINN | Partial Approval | Entered by CBELL1 - Room 1083 E. exterior wall OK to rock and tape. 1026 and 1027 OK to lid. |
01/23/2019 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Level 1 area 1083 west walls only |
01/22/2019 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Stairwell 2 only |
01/18/2019 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - area 1073 south wall only |
01/15/2019 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Level one room 1079 and hallway 1080 |
01/09/2019 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - level 1 rooms 1074, 1075, 1076, 1077 & 1078 |
01/02/2019 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Level 1 rooms 1082 & 1084 North wall room 1081 completing room 1081 |
12/26/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Level 1 GL B-C from 8-10 only |
12/21/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Maker space level one and two Except fire conduit north wall |
12/19/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Mechanical yard transformers and panels OK to energize for test to remain locked out and tagged out Level 1 core janitor closet and prayer room rooms 1025, 1026, 1027 and 1028 |
12/12/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Met with supers in office for egress path for temp c of o |
12/11/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Level 1 GL A-C from 3-6 only |
12/05/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Transformer and panels to L18 and 2L1B and electrical room 1010 OK to energize for test to remain locked out and tagged out |
12/05/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Level 1 GL 1-3 from A-B.7 only Elevator lobby wall level 1 |
12/04/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Electric room 1029 2 Transformers and all panels. Panels 1L21DF & 28HA OK TO ENERGIZE FOR TEST to remain locked out and tagged out |
12/03/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - See rfi 346 room 1013 |
11/20/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - stairwell 3 all levels exterior walls only |
11/14/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Level 1 slab garage GL-1-6 from A-E only |
11/13/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Switchhear SA & SB Panels CH1, CH2, air handler disconnects 1,2 &3 OK TO ENERGIZE FOR TEST To remain locked out tagged out |
11/07/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by VFLORES1 - Level 1 bathroom okay to insulate |
11/06/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - SES 1 switchgear OK TO ENERGIZE FOR TEST ECO to remain locked out tagged out |
11/05/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Shipping and receiving area only |
10/30/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Low voltage wiring West signs only |
10/29/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Level 2 GL A-C from 2-3 completes level 2 |
10/24/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Level 2 GL A-C from 5-6 Level 2 open offices 2022 & 2032 |
10/17/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - Level 2 core except electric rooms GL A-C from 6-10 |
10/12/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CBELL1 - GL 13-14 from A-C GL 10 -11 from A-B elevator lobbies 2000 & 3000 |
10/05/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CMURPHY1 - Level 2 rr rooms 206&209 |
10/03/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CMURPHY1 - Level 3 GL A-C from 4-6 only |
10/02/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CMURPHY1 - Level 3 restrooms 3008 & 3010 Level 1 rooms south of stairwell 1 rooms 1000s4V Demarc room 1017.1 level 1 |
09/27/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CMURPHY1 - Level 3 areas 4, 5 & 6 Rooms 3012 mkt stor, 3020 stor, 3019 hr stor, 3018 jan, 3017 hw, 3021 mothers, 3058 open office, 3065 open office, 3957 hw, 3064 hw, 3040 phone, 3041 focis, 3042 phone, 3044 huddle, 3045 phone, 3046 phone, 3047 focus, 3054 lg team, 3055 lg tram, 3056 huddle, 3051 focus, 3053 focus, 3063 phone, 3062 focus, 3061 phone, 3060 focus, 3014 phone, 3015 focus, 3016 phone, 3049 lg team & 3050 lg team. |
09/24/2018 | COT - HCEL - Electrical Intermediate | MRAMBER | Partial Approval | Entered by CMURPHY1 - zone 3 between C.L. 8-11 ok |
09/17/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CMURPHY1 - TES CALL CTR ROOM 3097 Elevator pit per detail 117 see rfi 281 10" oc each way top and bottom Rooms 3091, 3093, 3094, 3095, 3096 & 3097 GL A-C from 11-14 LEVEL 3 |
09/14/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by CMURPHY1 - Tes call center room 3597 Tes Tech Lab room 3096 Tes remote Moon Room 3095 Tes War Room 3094 open offices rooms 3091 and 3093 Mech yard only No test Shaft 1 condensate line only Mechanical shaft number 1 and 3 complete shaft number 2 except exhaust all hard duct GL 10 to 14 from A to C okay to insulate |
08/03/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Not ready for Inspection | Entered by RCAMACH1 - |
06/21/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by RCAMACH1 - ROOMS 2008, 2016, 3007 & 3022 GROUNDING |
05/23/2018 | COT - HCEL - Electrical Intermediate | BSTEVENS | Partial Approval | Entered by BSTEVENS - LEVEL 2 NORTH SLAB OK TO POUR |
05/18/2018 | COT - HCEL - Electrical Intermediate | RCAMACHO | Partial Approval | Entered by RCAMACH1 - ALL EXTERIOR CAD WELDS TO METAL COLUMNS AT BUILDING ONLY |