Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T17CM08216
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2021 | FIRE - FINAL | Approved | 1. Per inspector ross there was a list of deficiencies that needed to be corrected before a final could be given. The list of deficiencies have been corrrected and approved. | |
| 12/17/2021 | FIRE - FINAL | Partial Approval | 1.Just need stairwell signage and two way comunications fixed, | |
| 12/16/2021 | FIRE - FINAL | Partial Approval | P1 -missing sprinkler coverage in the room with the BDA equipment. -missing fire door at the elevator 3 vestibule -two way communication not working properly at elevator 3 -access to 2 concealed unprotected areas needs to be secured and sign added "Access Prohibited" or fire sprinklers and alarm devices need to be added. P2 -fire door at elevator 3 vestibule not closing properly 1st Floor -Exit sign at west exit to courtyard not working/missing -Exit signs and emergency lights not installed in hallways by maintenance room -Unit electrical panels need breaker schedules -Unit doors needs to be completed (weather-strips and thresholds) and tested. 2nd Floor -Exit sign by stair 1 is missing 3rd Floor -Stair 1 door not closing properly Signage for the Fire Pump Test Header needs to be corrected. Signage in the stairwells needs to meet the code requirements. 1023.9 Stairway identification signs. A sign shall be provided at each floor landing in an interior exit stairway and ramp connecting more than three stories designating the floor level, the terminus of the top and bottom of the interior exit stairway and ramp and the identification of the stairway or ramp. The signage shall state the story of, and the direction to, the exit discharge and the availability of roof access from the interior exit stairway and ramp for the fire department. The sign shall be located 5 feet above the floor landing in a position that is readily visible when the doors are in the open and closed positions. In addition to the stairway identification sign, a floor-level sign in visual characters, raised character and braille complying with ICC A117.1 shall be located at each floor-level landing adjacent to the door leading from the interior exit stairway and ramp into the corridor to identify the floor level. 1023.9.1 Signage requirements. Stairway identification signs shall comply with all of the following requirements. The signs shall be a minimum size of 18 inches by 12 inches. The letters designating the identification of the interior exit stairway and ramp shall be not less than 1 1/2 inches in height. The number designating the floor level shall be not less than 5 inches in height and located in the center of the sign. Other lettering and numbers shall be not less than 1 inch in height. Characters and their background shall have a non-glare finish. Characters shall contrast with their background, with either light characters on a dark background or dark characters on a light background. |
|
| 10/08/2021 | FIRE - FINAL | Prior to Intermediates | I added keys to all knox boxes. One knox box still needs to be installed at the NW stairwell. | |
| 09/22/2021 | FIRE - FINAL | Partial Approval | OK to obtain TCO from the building department for entire building except for units 122, 124,126,128,130 & 132 and the hallway in front of these unit. TCO IS ZERO OCCUPANCY-INSURANCE PURPSES ONLY |
|
| 08/23/2021 | FIRE - FINAL | Partial Approval | OK to obtain TCO for builder's insurance. Buildings A&B, C&D |
|
| 04/05/2021 | FIRE - FINAL | Partial Approval | Building A 1st-6th floors residential units - except: RM 557 sprinkler head in w/h closet needs adjustment and escutcheon RM 355 - head in bedroom - check for leak RM 154 - missing 2 smoke alarms throughout - adjust front doors to self close and latch |