Permit: T17CM08216

Parcel: 11720016G


Addresses:

110 S CHURCH AV


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T17CM08216

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/28/2021 PLUMBING - INTERMEDIATE Approved Approved. Buildings A,B, C, D, E, F, G, H, I, Garage: Room Units,corridors, common areas on floors #1 - 6.
05/03/2021 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #6; Room Unit 642.
03/26/2021 PLUMBING - INTERMEDIATE Denied Denied. No contact information, please call your inspector for further information to set up an inspection. Called main office, referred me to a superintendent, call number and left a message.
03/16/2021 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #6; Room Units 608; 628; 632
01/27/2021 PLUMBING - INTERMEDIATE Partial Approval Partial. Level B-2; Room Units 122; 124; 126; 128; 130.
01/11/2021 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #6; Room Units 641; 643; 644;:646; 648
01/06/2021 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #1; Area C-D Amenities areas. Walls only.
12/23/2020 PLUMBING - INTERMEDIATE Partial Approval . Partial. Level #4; Room Units 441; 442; 443; 446; 448
12/18/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Section H, Level #3; Room Units 341; 342; 343; 344; 346; 348.
Level #6; Room Units 623; 625; 626; 627; 630.
12/08/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #2; Section G, Room Units 241; 243; 244; 246; 248. Level #5; Section H; Room Units 523; 524; 525; 526; 527; 528; 530; 532.
12/07/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled, will reschedule for 8 December.
12/03/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Room Units 102; 104; 106. 108; 112.
12/01/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Level 6; Section I; Room Units 631; 633; 634; 635; 636; 637; 638; 639; 640.
11/17/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #5; Section I; Room Units 531-540. Domestic water lines on Levels #2 & Level 3 (3/4” Pex lines under test).
11/13/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled
11/05/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Section I, Level #4 Room Units 431-440. Ok to insulate and cover walls.
10/23/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #4; Section C; Room Units: 423; 424; 425; 426; 427; 428; 430; 432.
10/21/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #3; Section H, Room Units 323; 324; 325; 326; 327; 328; 330; 332.
10/20/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #3; Room Units 331; 333; 334; 335; 336; 337; 338; 339; 340.
10/16/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #2; Section I; Room Units 231; 233; 234; 235; 236; 237; 238; 239; 240.
10/13/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Section I, Level 2, units 231 thru 240.
10/02/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #2; Section I Room Units 223; 224; 225; 226; 227; 228
09/30/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #1; 6” Main water line: under test at 100 psi. Level #2; Section I, 4” lines under test at 100 psi; Room Units pex lines under test at 120 psi.
09/21/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled.
09/18/2020 PLUMBING - INTERMEDIATE Partial Approval Plumbing. Partial. DWV only.
Level 4. Units 432, 430. 428. 426. 427. 425. 423. 424.

Level 5. Units 524. 523. 525. 526. 527. 528. 530. 532

Level 6. Units 623. 630. 628. 627. 626. 626. 623. 624
09/03/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Waste and vent lines in Room Units #512; 515 on Level,#5.
09/02/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled will reschedule for 3 September
08/27/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Domestic water lines (pex lines) on Level #1, Room Units 24-32; Level #2, Room Units 223-232; Level #3 Room Units 323-332.
08/26/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #4; Room Units 412; 415; 417; 421; 422.
08/25/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled. Will reschedule for 26 August.
08/24/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #2; Section H: Room Units #224; 226; 228; 230. Domestic water lines (pex lines) hot and cold.
08/21/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled.
08/20/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Waste and vent lines at 2”-8” Levels: P1; P2; Levels #1-3 in Building H.
08/19/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #3; Room Units #312-322
08/10/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled.
07/31/2020 PLUMBING - INTERMEDIATE Partial Approval . Partial. Building C; Level #2; Room Units #217; 219; 220; 221; 222.
07/29/2020 PLUMBING - INTERMEDIATE Partial Approval Partial; Building C; Level #6; Room Units #604; 606; 610; 645; 609. Building D; Level #2; Room Units #212; 215.
07/27/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled.
07/16/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled, will reschedule for 17 July.
07/13/2020 PLUMBING - INTERMEDIATE Partial Approval . Partial. 8 inch sewer line from Buildings A-B and C-D to main sewer line in street. Ok to cover progress areas.
07/06/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled.
07/02/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Plumbing waste and vent lines; domestic hot/cold pex lines in Room units at Level #5; 512; 515; 517; 519; 520; 521; 522; 523. Level #6; Room Units #612; 615; 617; 619; 620; 621; 622; 623.
07/01/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #4; domestic pex lines in Room units #412; 415; 417; 419; 420; 421; 422; 423; 424.
06/29/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #5:Room units #502; 504; 506; 508; 509; 510; 511; 545.
06/23/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Level #4; plumbing in walls T 402; 404; 406; 408; 409; 410; 411; 445.
06/22/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled.
06/12/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Level#3; Ceiling areas in Rooms: 300; 302; 306; 308; 308; 309; 310; 311; 345.
06/05/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Waste and vent lines (2”-6”) at Levels #1-4; Rooms #112-422
05/29/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Not ready. Contractor canceled. Man hole is outside the site perimeter, Pima County.
05/26/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Not ready. Contractor canceled.
05/21/2020 PLUMBING - INTERMEDIATE Partial Approval Partial. Buildings C and D, Unit Rooms #200; 202; 204; 206; 208; 209; 210; 211; 245.
05/20/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled.
05/19/2020 PLUMBING - INTERMEDIATE Cancelled
04/13/2020 PLUMBING - INTERMEDIATE Partial Approval Inspection completed on 10 April by B Stevens
04/10/2020 PLUMBING - INTERMEDIATE Partial Approval RVI
SECTION C&D DOMESTIC WATER TEST LEVELS 4,5,6 140 PSI OK
DWV LEVEL 4 UNITS 402, 404, 406, 408, 410, 409, 411, 443/445 PARTY WALL OK TO COVER
04/08/2020 PLUMBING - INTERMEDIATE Not ready for Inspection CONTRACTOR CANCELLED.
03/18/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled
03/17/2020 PLUMBING - INTERMEDIATE Partial Approval Buildings C & D, Level #3, Domestic water lines under test at 120 psi.
03/13/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Contractor cancelled.
03/12/2020 PLUMBING - INTERMEDIATE Partial Approval Waste and vent lines (2"-6") at Basement level #1 North; Level #1; Units #102; 104; 106; 108 and public restrooms (112); Level #2; units: 200; 202; 204; 206; 208; 210; 211; 212 (North); 215 (North); 245. Domestic water lines at Levels 1-3; under test at 150 psi. In Sections A; B; C
03/10/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Contractor cancelled
02/28/2020 PLUMBING - INTERMEDIATE Partial Approval Level #6; Buildings A & B, Rooms: 650; 652; 654; 655; 656; 657,
02/05/2020 PLUMBING - INTERMEDIATE Partial Approval Level #5; waste and vent lines and domestic water lines in rooms: 550; 552; 553; 554; 555; 556; 557
02/03/2020 PLUMBING - INTERMEDIATE Partial Approval Level #1; domestic lines and waste and vent lines in rooms: 150; 152; 153; 154; 155; 156; 157. Buildings A & B
01/28/2020 PLUMBING - INTERMEDIATE Partial Approval Buildings A & B, Level #4; Rooms: 450; 452; 453; 454; 455; 456; 457.
01/27/2020 PLUMBING - INTERMEDIATE Partial Approval Level #3; Rooms: 350; 352; 353; 354; 355; 356; 357; in buildings A & B.
01/24/2020 PLUMBING - INTERMEDIATE Partial Approval Level #2; Buildings A & B; Rooms 250; 252; 253; 254; 255; 256; 257.
01/23/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Contractor cancelled.
01/15/2020 PLUMBING - INTERMEDIATE Partial Approval Primary and over-flow drains (8); Levels #1-6; under test.
01/14/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Primary roof drains were not under test.
01/13/2020 PLUMBING - INTERMEDIATE Partial Approval Buildings A & B; drains; waste and vent lines (2"-6"). Domestic hot and cold water lines (3/4"-2 1/2"). Levels #4; 5; 6.
01/09/2020 PLUMBING - INTERMEDIATE Not ready for Inspection Contractor cancelled.
01/02/2020 PLUMBING - INTERMEDIATE Partial Approval Buildings A & B; Level #2; Rooms 250; 252; 253; 254; 255; 256; 257.
12/18/2019 PLUMBING - INTERMEDIATE Not ready for Inspection Contractor cancelled due to heavy winds, unable to use crane.
12/17/2019 PLUMBING - INTERMEDIATE Not ready for Inspection Contractor cancelled.
12/10/2019 PLUMBING - INTERMEDIATE Partial Approval Level #3; Buildings A & B; Rooms: waste and vent lines; domestic hot and cold water lines.
12/09/2019 PLUMBING - INTERMEDIATE Partial Approval Waste and vent lines; pex domestic water lines in rooms on Levels #1 & 2: Buildings A & B.
04/23/2019 PLUMBING - INTERMEDIATE Not ready for Inspection no work