Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/26/2018 |
FRAMING |
|
Approved |
|
| 12/22/2017 |
FRAMING |
|
Denied |
PLAN IS CALLING FOR A TWO HOUR RATED SEPERATION WALL HOWEVER THAT IS NOT WHAT HAS BEEN CONSTRUCTED. THE BUILDING IS VB CONSTRUCTION AND IS UNDER THE ALLOWABLE AREA TO CONSIDERED THE TWO SUITES NON-SEPERATED USE. RECOMMENDED THE APPLICANT SUBMITS A REVISION TO ELIMINATE THE FIREWALL WITH THE ACCEPTANCE FROM THE ARCHITECT. |