Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2019 | BUILDING - FINAL | Partial Approval | full approval only pending fire departments approval they are scheduled to inspect today as well. | |
| 08/14/2019 | BUILDING - FINAL | Approved | ||
| 07/31/2019 | BUILDING - FINAL | Denied | 1- Shall provide locking caps on the condenser units refrigerant service ports. 2- Shall remove the adhesive tape on the insulation on the condenser line sets and provide up resistant zip ties. 3- Shall provide circuit breakers that match the max fuse spec for the condenser units. 4- Shall number label the circuit breakers in the sub panels. |
|
| 07/03/2019 | BUILDING - FINAL | Partial Approval | Partial approval to make application for Temporary Certificate of Occupancy for the purpose of funding only. Not for occupation or moving in furniture. | |
| 07/01/2019 | BUILDING - FINAL | Not ready for Inspection | Working for a Temporary Certificate of Occupancy to move in furniture and related equipment. Fire inspections must be performed before Temp C of O inspections can be performed. Will be recalled on 3 July. |