Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T17CM07498
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/15/2018 | PLUMBING - INTERMEDIATE | Approved | ||
06/13/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1 (EAST), MRI ROOM HEAT EXCHANGER (1 1/2" LINES TESTEFD AT 60 PSI) OK TO INSULATE | |
05/23/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #3, WEST PORTION: BLENDED HOT WATER - CHILLED WATE LINES 3/4" - 4" TESTED AT 100 PSI. OK TO INSULATE LINES | |
05/04/2018 | PLUMBING - INTERMEDIATE | Not ready for Inspection | LEVEL #3, EAST: CHILLED BEAM WATER LINES TESTED AT 80 PSI: REQUIRED TO BE TESTED AT 100 PSI. | |
03/21/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #3, EATS PORTION: HEATED HOT WATER SYSTEM LINES AT 34" - 2 1/2". OK TO INSULATE PROGRESS AREAS. | |
03/16/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #3, EAST: HEATED HOT WATER - 3/4" - 2" LINES; (NORTH AND EAST AREAS). | |
03/14/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #3, EST: DOMESTIC HOT/COLD WATER LINES: 1/2" - 2": ALL LINES UNDER TEST AT 100 PSI. | |
03/06/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #3, WEST: WASTE AND VENT LINES AT 2" - 4"; GL: D-G/3-7 | |
03/01/2018 | PLUMBING - INTERMEDIATE | Partial Approval | DOMESTIC HOT AND COLD WATER LINES (1/2" - 2") : BATHROOMS AND LAVS AT GL: F-G/14. | |
02/28/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #3, EAST: WASTE AND VENT LINES AT GL: F-G/14-17; 2" - 4" LINES TESTED AT 7 PSI. DOMESTIC HOT AND COLD WATER LINES (IN WALLS), GL: E- G.5/15-18 (1/2" - 2") LINES, TESTED AT 100PSI. OK TO INSULATE PROGRESS AREAS. | |
02/27/2018 | PLUMBING - INTERMEDIATE | Partial Approval | WASTE AND VENT LINES (2" - 4") AT GL: D-H/14-19 AT LEVEL #3; EAST PORTION OF BUILDING. | |
01/16/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #3, EAST, 1 1/2" WASTE LINES UNDER TEST EXCEPT FOR AREAS G-17, G-16 (GAUGES NOT UP TO TEST LEVEL) |