Inspection Status: Passed
Inspection History: RSEL - Electrical Progress
| Date |
Description |
Inspector |
Results |
Comments |
| 08/30/2019 |
RSEL - Electrical Progress
|
RCHANDLER |
Approved |
Entered by DMERANZ1 - |
| 09/11/2018 |
RSEL - Electrical Progress
|
GWest |
Partial Approval |
Entered by GWEST2 - Light and proximal switch required at exit door and in attic at crawl space opening. Secure all romex in attic at 4'OC. Secure all romex 6 " before it enters a J-Box. Receptacle required in Hallway. Smoke detectors required at hallway leading to bedroom and one in the bedroom. Bond all metal boxes with a pigtail long enough to connect to the ground wires entering th J-Boxes using metal J-Boxes. Laundry- use single Yoke receptacles at J-Boxes provided for the Washer and the Dryer. |