Permit: T17CM04982

Parcel: 11712099A


Addresses:

20 S STONE AV


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T17CM04982

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/15/2020 FIRE - FINAL Approved All issues have been addrtessed and rectified
07/02/2020 FIRE - FINAL Partial Approval Alarm permit has outstanding fees
05/29/2020 FIRE - FINAL Partial Approval APPROVED TO OBTAIN TCO FOR FULL OCCUPANCY
05/19/2020 FIRE - FINAL Partial Approval Unit 619 drywall around sprinkler head
615 kitchen head had a cap needed trim
601 kitchen head needed adjustment
602 entry head needed adjustment
602 kitchen head needed adjustment
605 bed 1 needed adjustment
606 appliances were in the way could not see head
607 appliances were in the way could not see head
610 mechanical room had a cap on needed trim
Level 4 re test duct detector unit wouldn’t shut down
A-phones need signage (what level you are on)
Emergency lighting level 1
Smoke alarms in units (5)
Fire alarms amenity, lobby, coworking area. Level 1
Unit 211,205 ADA fire alarm send supervisory only to panel (Scott we will need 5 low frequency sounders and strobe )that will tie into your system.
Check stair 2 for correct addressing level 2 fire alarm
Scotts fire proper labeling of panels in electrical rooms
Knox key box under A-phone level 1 elevator
Fire sprinkler sign at FDC ( AL sent you a picture of what is needed GPM & PSI )
Address sign
Test Knox key lock entry lobby
Sprinkler final level 1
AL fire department is asking for stand pipe test at roof at the pressure we are at
Store fronts corridor 126 north & corridor 128 south fire rating ?
1 south church stand pipe identification P-1 & P-3
Sign at east door exit passage way 130 ( pump room inside )
Need to get this completed so we can schedule inspection thank you
05/19/2020 FIRE - FINAL Partial Approval NOTES: DOOR HARDWARE NEEDS TO BE FIRE RATED AND WILL TAKE A WHILE TO GET IN
STAIRWELL DOOR CARD ACCESS TO BE REMOVED FOREVER
SIGNAGE REQUIRED ON THE BUILDING INCLUDING ADDRESS
PUMP ROOM REQUIRES 1 HOUR RATED CORRIDOR NEED TO CONFIRM THAT THE GLASS AT THE END OF HALL WAY IS FIRE RATED
TEST THE KEY SWITCH AND CARD ACCESS
INSTALL KEYS INTO THE LOCK BOX AND ELEVATOR BOXES
05/15/2020 FIRE - FINAL Partial Approval 619 drywall patch around head
615 kitchen head had the cap
601 kitchen head needed adjustment
602 entry head needed adjustment
602 kitchen head needed adjustment
605 bed 1 needed adjustment
606 appliances were in the way couldn’t see head
607 appliances were in the way couldn’t see head
610 mechanical room had a cap
04/22/2020 FIRE - FINAL Partial Approval We have tested and commissioned the fire pump and fire sprinkler systems for the building. The systems are live, operational and will dispatch TFD if needed. TFD ok with TCO to FUND with approval from COT PDSD.