Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T17CM04982
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2020 | FIRE - FINAL | Approved | All issues have been addrtessed and rectified | |
| 07/02/2020 | FIRE - FINAL | Partial Approval | Alarm permit has outstanding fees | |
| 05/29/2020 | FIRE - FINAL | Partial Approval | APPROVED TO OBTAIN TCO FOR FULL OCCUPANCY | |
| 05/19/2020 | FIRE - FINAL | Partial Approval | Unit 619 drywall around sprinkler head 615 kitchen head had a cap needed trim 601 kitchen head needed adjustment 602 entry head needed adjustment 602 kitchen head needed adjustment 605 bed 1 needed adjustment 606 appliances were in the way could not see head 607 appliances were in the way could not see head 610 mechanical room had a cap on needed trim Level 4 re test duct detector unit wouldn’t shut down A-phones need signage (what level you are on) Emergency lighting level 1 Smoke alarms in units (5) Fire alarms amenity, lobby, coworking area. Level 1 Unit 211,205 ADA fire alarm send supervisory only to panel (Scott we will need 5 low frequency sounders and strobe )that will tie into your system. Check stair 2 for correct addressing level 2 fire alarm Scotts fire proper labeling of panels in electrical rooms Knox key box under A-phone level 1 elevator Fire sprinkler sign at FDC ( AL sent you a picture of what is needed GPM & PSI ) Address sign Test Knox key lock entry lobby Sprinkler final level 1 AL fire department is asking for stand pipe test at roof at the pressure we are at Store fronts corridor 126 north & corridor 128 south fire rating ? 1 south church stand pipe identification P-1 & P-3 Sign at east door exit passage way 130 ( pump room inside ) Need to get this completed so we can schedule inspection thank you |
|
| 05/19/2020 | FIRE - FINAL | Partial Approval | NOTES: DOOR HARDWARE NEEDS TO BE FIRE RATED AND WILL TAKE A WHILE TO GET IN STAIRWELL DOOR CARD ACCESS TO BE REMOVED FOREVER SIGNAGE REQUIRED ON THE BUILDING INCLUDING ADDRESS PUMP ROOM REQUIRES 1 HOUR RATED CORRIDOR NEED TO CONFIRM THAT THE GLASS AT THE END OF HALL WAY IS FIRE RATED TEST THE KEY SWITCH AND CARD ACCESS INSTALL KEYS INTO THE LOCK BOX AND ELEVATOR BOXES |
|
| 05/15/2020 | FIRE - FINAL | Partial Approval | 619 drywall patch around head 615 kitchen head had the cap 601 kitchen head needed adjustment 602 entry head needed adjustment 602 kitchen head needed adjustment 605 bed 1 needed adjustment 606 appliances were in the way couldn’t see head 607 appliances were in the way couldn’t see head 610 mechanical room had a cap |
|
| 04/22/2020 | FIRE - FINAL | Partial Approval | We have tested and commissioned the fire pump and fire sprinkler systems for the building. The systems are live, operational and will dispatch TFD if needed. TFD ok with TCO to FUND with approval from COT PDSD. |