Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T17CM04810
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/08/2018 | FIRE SPKLR - FINAL | Approved | ||
05/04/2018 | FIRE SPKLR - FINAL | Partial Approval | Still need full sprink final. These are notes from OH. 1) Add bracing to top of 6" riser on upper floor. 2) Add missing FDC. 3) Add bracing to riser in riser room. 4) Knox FDC plugs. (they have been ordered) 5) Mount spare head box, calc plate. |