Permit: T17CM03512

Parcel: 14043013B

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T17CM03512

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/15/2022 FIRE - FINAL Approved ERRC provided by Raytheon from Modtech portable unit and approved by Chief Ryan. System is not code compliant, not monitored and will be stored and maintained by Raytheon. Approved for COFO.
10/22/2019 FIRE - FINAL Partial Approval EVERYTHING IS COMPLETE ON THE BUILDING EXCEPT FOR THE EMERGENCY RESPONDER RADIO COVERAGE THAT RAYTHEON NEEDS TO PROVIDE
09/11/2019 FIRE - FINAL Partial Approval 2 way communication needs 4 IP addresses to work properly
Everything else on the fire list was cleared
COFO WILL NOT BE ISSUED WITHOUT EMERGENCY RESPONDER RADIO COVERAGE APPROVED & FINAL
03/15/2019 FIRE - FINAL Partial Approval Add exit signs by colums G6 & F4
2 way communication needs 4 IP addresses to work properly
Everything else on the fire list was cleared
COFO WILL NOT BE ISSUED WITHOUT EMERGENCY RESPONDER RADIO COVERAGE APPROVED & FINAL
10/24/2018 FIRE - FINAL Partial Approval OK to obtain a TCO
10/18/2018 FIRE - FINAL Partial Approval Exit light 3rd loor SE needs to have the chevron added
Panel scheules need to be in each electrical panel
Panels need to be labeled
Fire smoke dampers labeled 1/2" letters
Maglocks on front door need to be connected to the fire alarm system
Unclassified office needs double sided exit signs
Add exit sign double doors by housekeeping both floors
Remove all temporary lighting fixtures
Generator needs to be monitored by the fire alarm
Generator needs to kick on within 30 seconds