Inspection History: FIRE - ALARM FINAL

Permit Number - T17CM03512

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/19/2019 FIRE - ALARM FINAL Approved
03/15/2019 FIRE - ALARM FINAL Partial Approval See T17FC00955
10/18/2018 FIRE - ALARM FINAL Partial Approval Add h/s outside storage A0110
Change H/S to Strobe only in bathrooms 1B0110, 1B0130, and change to 30 candella
Change H/s to Strobe only wellness room 1 B0255
Change Front Lobby HS to 95 Candella
Change 2 h/s office 1B0200 from 15 cd to 75 cd
Change Conference room 1B0315h/s to 30 candella
All team rooms in the building need to be strobe only and 15 candella
Add H/S to corridor outside conference #9
Office 1163? H/S not working properly
conference room #6 change from 15cd to 30cd
Bathroom 1J0310 and 1J0320 need to be strobe only
change h/s in wellness room #1B0655 to strobe only
Add manual pull station to office 1B0200 by north door
Conference room # 15 is 15 csandella and needs to be 30
Bathroom #1C0545 & 1C0525 need to be changed to strobe only
Office #13 hs back area is 15 cd and needs to be 75 cd
Office #12 front h/s is not working and needs to be replaced
Vestibule # 10 replace the h/s with a 15 cd strobe only
2 H/s Main electrical room need to be raised to the proper height
All power supplies to have a red breaker labels Fire Alarm
Mag locks on the front door need to be connected to the fire alarm
Level 2 area add notification corridor 2.3 by conference room 200295
All Team rooms 5,7,9& 10 need to be changed to strobe only devices
Conference Room # 17 & 18 need to be changed to 30 candella
East side restroom needs to be changed to 30 candella
08/16/2018 FIRE - ALARM FINAL Partial Approval Only checked the signals for the fire sprinkler water flow and tamper. All set at 40-42 seconds per Jim Tucker. Fire alarm has one more inspection. Any inspections past that will need to be paid for prior to calling a final back in.