Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2017 | MECHANICAL - INTERMEDIATE | Approved | ||
| 08/02/2017 | MECHANICAL - INTERMEDIATE | Cancelled | ||
| 07/31/2017 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | ANSUL SYSTEM NOT INSTALLED YET | |
| 07/28/2017 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | ||
| 07/25/2017 | MECHANICAL - INTERMEDIATE | Partial Approval | GREASE DUCT ALL OK. WRAP IS APPROVED | |
| 07/24/2017 | MECHANICAL - INTERMEDIATE | Partial Approval | SMOKE TEST PASSED, OK TO WRAP. FIRST LAYER OF WRAP OK TO COVER. |
|
| 07/10/2017 | MECHANICAL - INTERMEDIATE | Partial Approval | APPROVED WITH THE EXCEPTION OF THE HOOD. LIGHT AND SMOKE TEST REQUIRED TO VERIFY EXISTING HOOD IS LEAK FREE. ACCESS REQUIRED PER 2012 IMC. VERIFY IF HEAT SWITCH IS NOT REQUIRED OR INSTALLED THE SWITHC PER 2012 IMC, IFC, AND 20112 NEC |