Permit: T17CM02882

Parcel: 103190410

Inspection Status: Passed

Inspection History: COT - RSEL - Grounding/Bonding 

Permit Number - T17CM02882

Inspection Description - COT - RSEL - Grounding/Bonding 

Inspection Status - Passed

Date Description Inspector Results Comments
02/03/2020 COT - RSEL - Grounding/Bonding  DQUINN Approved Entered by DMERANZ1 -
01/30/2020 COT - RSEL - Grounding/Bonding  TVALENCIA Denied Entered by DMERANZ1 - 1- Shall provide 18 inches of cover from top of conduit piping to finish grade. Reference Table E3803.1 2012 IRC
05/17/2019 COT - RSEL - Grounding/Bonding  TVALENCIA Partial Approval Entered by CBELL1 - 1- 20 feet of copper #4 Ufer conductor provided in footing.
05/14/2019 COT - RSEL - Grounding/Bonding  TVALENCIA Partial Approval Entered by CBELL1 - 1- Shall complete forms for footing and slab. 2- Reference footing detail 1 S-1 showing the top rebar. 3- Shall wrap plumbing risers and any plumbing in concrete. 4- 20 feet of copper Ufer has been provided.