Permit: T17CM02636

Parcel: 14043013B

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T17CM02636

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/28/2019 MECHANICAL - INTERMEDIATE Approved
12/20/2018 MECHANICAL - INTERMEDIATE Partial Approval 100 pound test chiller system and hot water line system 90 foot roof OK to insulate
12/13/2018 MECHANICAL - INTERMEDIATE Partial Approval galley room J0 510 janitor closet J0 520 and water closet room J0 530 OK to insulate water lines
12/13/2018 MECHANICAL - INTERMEDIATE Partial Approval Galley room J0510, janitors closet J0520 & water closet room J0530
Ok to insulate hot water lines
11/13/2018 MECHANICAL - INTERMEDIATE Partial Approval Entire heating water system except Riser riser to 90 foot roof 100 lb test
11/07/2018 MECHANICAL - INTERMEDIATE Partial Approval Hot water and chill water systems on mid roof 100 psi test ok to insulate both systems
10/31/2018 MECHANICAL - INTERMEDIATE Partial Approval Chill water mid-roof North system 100 PSI test okay to insulate
09/21/2018 MECHANICAL - INTERMEDIATE Partial Approval 100 psi test chill water whole system in luding east roof
09/11/2018 MECHANICAL - INTERMEDIATE Partial Approval
09/05/2018 MECHANICAL - INTERMEDIATE Partial Approval HOT WATER LINES 5 UNITS ROOM E0600 OK TO INSULATE 100 LB TEST OK
08/31/2018 MECHANICAL - INTERMEDIATE Not ready for Inspection
08/14/2018 MECHANICAL - INTERMEDIATE Partial Approval HHW hydro test ok at interior piping
08/10/2018 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/10/2018 MECHANICAL - INTERMEDIATE Partial Approval 100 PSI COMPLETION OF CHILLED WATER SYSTEM AT ROOF
07/19/2018 MECHANICAL - INTERMEDIATE Partial Approval CHILLED WATER LINES TEST 100 PSI GL G THROUGH CORRIDOR D0700 THRU GL WALL 7.1 OK TO INSULATE
07/18/2018 MECHANICAL - INTERMEDIATE Not ready for Inspection
07/17/2018 MECHANICAL - INTERMEDIATE Not ready for Inspection
07/16/2018 MECHANICAL - INTERMEDIATE Not ready for Inspection NO WORK
06/25/2018 MECHANICAL - INTERMEDIATE Not ready for Inspection
06/13/2018 MECHANICAL - INTERMEDIATE Partial Approval HEATING WATER VAV1-1 TO 1.2, 1.3, 1.5, 1.6 & 1.7 ONLY 120 LB TEST TERMINATING ABOVE DUCT GRID LINE 7.2 TO D.5
OK TO INSULATE
06/07/2018 MECHANICAL - INTERMEDIATE Partial Approval TEST AT HOT WATER CHILLER LINES AT PUMP HOUSE
06/01/2018 MECHANICAL - INTERMEDIATE Partial Approval CHILLED WATER SUPPLY AND RETURN LINES PRESSURE TEST WEEST OF GRID LINE G OK TO INSULATE
05/07/2018 MECHANICAL - INTERMEDIATE Partial Approval DUCTS OK TO INSULATE GRID LINES D-E 1-7.1, Q-P 1=8
04/10/2018 MECHANICAL - INTERMEDIATE Partial Approval INFO ONLY
04/04/2018 MECHANICAL - INTERMEDIATE Partial Approval AREA F HEATING WATER AND COMPRESSED AIR 150 PSI AND120 PSI TESTS OK