Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T17CM02634
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/27/2019 | PLUMBING - YARD WTR LINE/TEST | Approved | ||
07/13/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | riser at C.U.P. bldg ok | |
06/21/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | DATA CENTER ONLY TO BE TESTED AT TLATER DATE | |
03/21/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 200# TEST ON 4" SUPPLY FOR MPB OK | |
03/01/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | approx 40' 3" through bckflow to 3' of mpb tie in | |
02/22/2018 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | ||
02/21/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 210 psi test on 8' WATER LINE FROM SW ATF HYDRANT TO SE ISOLATION VALVES | |
02/15/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 200 psi test on 8" water line approx 600' from tie in to valves on south side mpb | |
02/14/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 205 psi test on approx 1000' 8" lines north and east sides atf. | |
02/09/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | approx 80' 8" water line going west on south side mpb | |
02/08/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 8" water line running west from atf | |
02/05/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 1 1/2" irrigation line from 8" main heading east on west side atf | |
02/02/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | thrust block at south west fire hydrant ok, 6" fire line from main to piv at center west of atf' 4" domestic water center west atf approx 30' ok | |
02/01/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 6" fire line sw corner atf to hydrant | |
01/30/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | approx. 200' of 8" water line at north side of atf | |
01/23/2018 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | ||
01/22/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 1 1/2" CPPOER LINE APPROX 20' NE CORNER MPB FOR LANDSCAPE | |
01/18/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 200 LB TEST FROM HOT TAP TO 1ST VALVE NW OF TAP ONLY | |
01/09/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 300' OF 8" LINE SOUTH OF ATF TO BE TESTED AT A LATER DATE | |
01/08/2018 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 200 LB TEST FROM TAP AT SW CORNER MPB TO 2ND HYDRANT NW | |
12/27/2017 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | fire line to be inspected by F.D. | |
12/12/2017 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | NO WORK | |
12/11/2017 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | CANCELED | |
12/08/2017 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | WORK NOT COMPLETE | |
12/07/2017 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | AFTER HOURS APA ACCOUNT$165.00 DROP DOWN UNDER CHILLER LINES SOUTH OF ROAD FROM "T" 30' OF 8" LINE TO BE TESTED AT A LATER DATE |
|
12/06/2017 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 8" LINE 120' UP TO VALVE NORTH OF TEST FACILITY TO BE TESTED AT A LATER DATE | |
12/05/2017 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 12" LINE FROM VALVES TO 80' EAST TO BE TESTES AT A LATER DATE | |
12/04/2017 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 60' OF 8" LINE ACROSS ROAD ONLY TO BE TESTED AT A LATER DATE | |
12/01/2017 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 160' OF 8" LINE FROM "T" TO SOUTH EAST OF MULTI PURPOSE BUILDING | |
11/30/2017 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | INSULATION AND WRAP 11/29 INSPECTION AREAS ONLY | |
11/29/2017 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 140' FROM 90 EAST OF MULTI PURPOSE BUILDING TO BE TESTED AT A LATER DATE |
|
11/28/2017 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | AFTER HOURS APA ACCOUNT $165.00 220' OF 8" LINE NORTH OF MULTI PURPOSE BUILDING UP TO 90 TO BE TESTED AT A LATER DATE |
|
11/22/2017 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 20' NORTH OF "T" TO 90 140' NORTH OF MULTI PURPOSE BUILDING TO BE TESTED AT A LATER DATE | |
11/21/2017 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 80' WEST OF MULTI PURPOSE BUILDING TO "T" ONLY | |
11/20/2017 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 240' west of multi purpose bldg ok to cover | |
11/16/2017 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | 6 COUPLINGS WITH RESTRAINING BOLTSS NORTH OF VALVE TAP 115' ONLY TO BE TESTED AT A LATER DATE SEE HIGHLIGHTED AREA |
|
11/15/2017 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | TAP AT CUP ONLY | |
11/03/2017 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | AFTER HOURS APA ACCOUNT $165.00 NEXT 2 COUPLING JOINTS NORTH AND EAST OF MULTI PURPOSE BUILDING RESTRAINING BOLTS OK T INSULATE AND WRAP ONLY CAP AND SLEEVE AT VALVE BY BUILDING 916 ONLY |