Permit: T17CM02633

Parcel: 14043013B

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T17CM02633

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/29/2019 FIRE - ALARM FINAL Approved
04/16/2019 FIRE - ALARM FINAL Partial Approval Need to install a manual pull station in the NE corner door of 926 A
926B small room needs a smoke detector relocated as it is to close to the supply/return air system.
926 A & B have open gutter and j boxes that need to have covers installed
926B Exit and Emergency Lights are not working
08/15/2018 FIRE - ALARM FINAL Partial Approval Only confirmed the water flow an dtamper signals to the central station. Water flow was set at 42 seconds per Jim Tucker