Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T17CM02114
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2019 | FIRE - FINAL | Approved | Restrictions to work on only one stairway at a time while finishing to have two remaining stairwells for egress. Exit being worked on show as closed. Extinguishers shall be labeled in all corridors Ceiling shall be sealed in mechanical room. Exterior gate doors shall remain unlocked until locking mechanisms are in place and fobs are available in knox boxes. Remove caps from smoke detectors in elevator mechanical room. Returning Monday to verify debris is moved from walkways. |
|
| 01/23/2019 | FIRE - FINAL | Partial Approval | 2nd floor complete and okay for TCO. Inspected 4th floor. Several corrections shall be made prior to next inspection. Re-inspection fee is added. | |
| 12/28/2018 | FIRE - FINAL | Partial Approval | OK FOR TCO 3RD FLOOR | |
| 12/28/2018 | FIRE - FINAL | Partial Approval | APPROVED TO OBTAIN TCO FOR 3RD FLOOR. | |
| 12/20/2018 | FIRE - FINAL | Partial Approval | Tested the fire alarm, fire sprinkler and smoke detectors for the 3rd floor. Ok fot TCO pending Building. | |
| 12/20/2018 | FIRE - FINAL | Partial Approval | Tested the fire alarm on all floors notes are on T18FC0080. Performed a walk of 1-4 fire sprinkler and the notes are on T18FC00064 (there are a lot that need to be remedied for COFO) Need to check KNOX boxes and Keys for Final, check gates and hardware and signage. |
|
| 11/30/2018 | FIRE - FINAL | Partial Approval | Verified that all exit and emergency egress ltg functioning. Gates at cortyard have no locking devices (panic hdwr. required for CofO). Temp address sign to be posted at SE corner of bldg. Future permanent address to be installed at east face at SE corner. Ok for TCO (spoke to Armando). |
|
| 11/29/2018 | FIRE - FINAL | Partial Approval | Tested the fire alarm and fire sprinklers today. Fire sprinkler is operational along with the fire alarm system. Both systems are operational and sending the signals to the fire department. Some items need to be corrected for the 1st floor prior to calling in for the COFO. The only otem missing for TCO from Glenn D'Aurias list was the emergency and exit lights. Half of the lights were working and some of them were out. Advised that they call back in tommorrow to go over with Glenn. TCO pending approval from GD @ TFD. 11/30/18 OK PER GD FOR TCO |