Permit: T17CM02114

Parcel: 116206330


Addresses:

855 W CONGRESS ST


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T17CM02114

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/24/2019 FIRE SPKLR - FINAL Approved
01/23/2019 FIRE SPKLR - FINAL Partial Approval Inspected 4th floor. Several corrections shall be made prior to next inspection. Re-inspection fee is added.
01/22/2019 FIRE SPKLR - FINAL Partial Approval 2nd floor complete and okay for TCO
01/17/2019 FIRE SPKLR - FINAL Denied Re-inspection fee added for next inspection.
2nd floor TCO inspection not granted.
*219 - Replace missing escucheon in closet
*219/218 or 217 fill in gap in closet
*217 MB escucheon
* 215 front closets (painted heads) taped, escucheon missing
* 214 seal gap
* 211 painted head right hallway
* 210 escucheon missing, painted head
* 209 missing light fixture in bathroom
* 208 escucheon missing front closet
* 207 sprinkler needs to be recessed
* 206 painted head, sink missing
- Make sure caps and tape are off FA horns and extinguishers in place.
11/29/2018 FIRE SPKLR - FINAL Partial Approval Room 111 closets have a total of 3 heads that are twisted
Room 111 bathroom has a head that needs to be replaced
Room 110 Kitchen area has a head that needs to be tweaked
Room 110 has a head in the bathroom that needs to be adjusted
Mechanical room on the 1st floor east area needs to have a head added because it is covered with drywall
Room 113 bedroom areas have 2 heads that need to be corrected
Room 113 has a head in the closet that has tape on it and needs an escutcheon added
Room 113 hallway head is painted and needs to be replaced
Room 115 bathroom head needs to be adjusted/ replaced
Room 104 has a painted head in the bathroom
Room 105 laundry room has a painted head
Room 107 head painted in the kitchen that also needs to be lowered since it is obstructed by the light fixture
Room 107 painted heads in the laundry and bathroom areas
Room 116 hall head needs to be corrected
Room 116 closet and hall heads are painted
Add head in the fire riser room
Add heads under the garage door in the basement
Add head in the mutli purpose room
Remove two heads in the hall outside of the offices
Rotate all hose connection so that they are not pointing in the down position.
The bike room has two heads that are painted
Need to extend the stanpipes to the roof for access
This was for the first floor only
07/10/2018 FIRE SPKLR - FINAL Partial Approval 1st floor all rooms have had the 200 psi for two hour test. 2nd floor corridor has been looked at but ony had 50 psi of street pressure and will need the 200 test before the rest of the rooms can be sheet rocked. Ok to sheet tock the hall ways on the 2nd floor.