Permit: T17CM01475

Parcel: 11712087B


Addresses:

2 E CONGRESS ST 05


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T17CM01475

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2017 FIRE - FINAL Approved
07/25/2017 FIRE - FINAL Partial Approval PA. This was an inspection for fourth floor only. Following notes are from fire alarm permit.
4th floor inspection only:
1) need to test NE flow and tamper (janitor closet). They are being replaced.
2) Need FF phones installed/tested.
3) Need to test talkaphones.
4) Dampers on 4th and 5th tested (they worked/approved).
5) Additional reinspection fee added. Must be paid prior to next inspection.
6) Some items from 5th floor still need approval. See items from previous list, #1, 3, 5.
APPROVED TO OBTAIN TCO FOR FULL OCCUPANCY ON 4TH FLOOR.

Some additional items needing correction.
-need sprinkler coverage in comm closets.
-need to install water curtain on 3rd floor windows next to fire exit.
06/30/2017 FIRE - FINAL Partial Approval This was an inspection for the 5th floor only. PA on 5th floor. Two outstanding violations. TCO for full occupancy approved if item #2 is resolved. Item #1 does not need to be completed for TCO.
1) See alarm notes under T17FC00280. Alarm on 5th floor only partial approved.
2) Still waiting on third party review for smoke control.