Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T17CM01475
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2017 | FIRE - FINAL | Approved | ||
07/25/2017 | FIRE - FINAL | Partial Approval | PA. This was an inspection for fourth floor only. Following notes are from fire alarm permit. 4th floor inspection only: 1) need to test NE flow and tamper (janitor closet). They are being replaced. 2) Need FF phones installed/tested. 3) Need to test talkaphones. 4) Dampers on 4th and 5th tested (they worked/approved). 5) Additional reinspection fee added. Must be paid prior to next inspection. 6) Some items from 5th floor still need approval. See items from previous list, #1, 3, 5. APPROVED TO OBTAIN TCO FOR FULL OCCUPANCY ON 4TH FLOOR. Some additional items needing correction. -need sprinkler coverage in comm closets. -need to install water curtain on 3rd floor windows next to fire exit. |
|
06/30/2017 | FIRE - FINAL | Partial Approval | This was an inspection for the 5th floor only. PA on 5th floor. Two outstanding violations. TCO for full occupancy approved if item #2 is resolved. Item #1 does not need to be completed for TCO. 1) See alarm notes under T17FC00280. Alarm on 5th floor only partial approved. 2) Still waiting on third party review for smoke control. |