Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2017 | FIRE - FINAL | Approved | ||
| 07/25/2017 | FIRE - FINAL | Partial Approval | APPROVED TO OBTAIN TCO FOR FULL OCCUPANCY ON 4TH FLOOR. PA. This was an inspection for fourth floor only. Following notes are from fire alarm permit. 4th floor inspection only: 1) need to test NE flow and tamper (janitor closet). They are being replaced. 2) Need FF phones installed/tested. 3) Need to test talkaphones. 4) Dampers on 4th and 5th tested (they worked/approved). 5) Additional reinspection fee added. Must be paid prior to next inspection. 6) Some items from 5th floor still need approval. See items from previous list, #1, 3, 5. APPROVED TO OBTAIN TCO FOR FULL OCCUPANCY ON 4TH FLOOR. Some additional items needing correction. -need sprinkler coverage in comm closets. -need to install water curtain on 3rd floor windows next to fire exit. |