Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T17CM01473
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2017 | FIRE - FINAL | Approved | ||
08/22/2017 | FIRE - FINAL | Partial Approval | Approved for TCO, full occupancy, 3rd floor. 3rd floor inspection only. 1) Need to test flow switch 4th floor once repaired. 2) Label smoke control panel. 3) As builts for sprinkler. 4) Proposal for stairwell illumination. 5) 9th floor fire rated construction. 6) Need as builts for alarm. 7) Water curtain 3rd floor ? 8) FF phone volume too low. 9) Need strobe in ADA room, bathroom. |