Case: T16DV05593

Parcel: 10612016A


Addresses:

1681 W PRINCE RD


Inspection Status: Approved

Inspection History: INSP - FOLLOW UP CODE ENFORCE

Case Number - T16DV05593

Inspection Description - INSP - FOLLOW UP CODE ENFORCE

Inspection Status - Approved

Date Description Inspector Results Comments
02/20/2018 INSP - FOLLOW UP CODE ENFORCE Approved PERMIT T16CM08513 FOR UNITS 1-27 PLUS LAUNDRY BUILDING. EXTENSIVE NOTES ADDED TO NOV. INSPECTOR SHOULD REVIEW PRIOR TO ARRIVAL (T16DV05593) WAS APPROVED ON 1-19-2018,, CLOSE CASE
08/02/2017 INSP - FOLLOW UP CODE ENFORCE Approved PERMIT T16CM08513 WAS REOPENED BY BO,, INSPECTIONS ARE CONTINUING.. PERMIT EXPIRES ON 10-18-2018
04/14/2017 INSP - FOLLOW UP CODE ENFORCE Approved PERMIT T16CM08513 UNITS 1-27 PLUS LAUNDRY BUILDING. EXTENSIVE NOTES ADDED TO NOV. INSPECTOR SHOULD REVIEW PRIOR TO ARRIVAL (T16DV05593) WAS FINAL ON 1-19-2017. THE SPACE VIOLATIONS TO THE EQUIPMENT DISCONNECTS WERE NOT ADDRESSED WILL CALL OWNER
12/16/2016 INSP - FOLLOW UP CODE ENFORCE Approved PERMIT ISSUED T16CM08513, FOLLOW UP INSPECTION
DUE 6-13-2017
10/04/2016 INSP - FOLLOW UP CODE ENFORCE Approved COMPLETED ALL INSPECTIONS:
SERVICE DISCONNECT FOR UNITS 1/ 11,D
THIS SERVICE IS LOCATED IN SPACE 3

1. VERIFY GROUNDING SYSTEM

2. UNUSED OPENING

3. MISSING DEAD FRONT FROM ENCLOSURE 11/D



SERVICE DISCONNECT FOR UNITS 12/17
THIS SERVICE IS LOCATED IN SPACE 15.

1. THERE IS A NON-METALLIC SHEATHED CABLE, (UNDERGROUND FEEDER) TYPE: WHICH RUNS FROM THE EARTH TO THE MAIN SERVICE WITH A 4 FOOT PORTION EXPOSED AND UNPROTECTED. IM UNABLE TO READ AMPACITY OF THE FEEDER.

2. UNABLE TO DETERMINE BREAKER AMPACITY FOR THE FOLLOWING MAIN BREAKERS: 12, 15 AND 17.

3. THE FOLLOWING MAIN BREAKERS HAVE MISSING PROTECTIVE COVERS: 13 AND 17.

SERVICE DISCONNECT LOCATION FOR UNITS 18,19,21,22,
THIS SERVICE IS LOCATED IN SPACE 19
1. MAIN BREAKER LABELED 23 IS AT OTHER LOCATION, UNKNOWN DESIGNATION

2. UNUSED OPENING

3. MAIN BREAKER 21 IS UNREADABLE

4. VERIFY GROUNDING SYSTEM

5. WORKING CLEARANCE IS OBSTRUCTED

6. TWO (2) INCH ELECTRICAL METALLIC TUBING (EMT) HAVE ERODED AT THE POINT THERE THEY MEET THE EARTH

7. (3) ELECTRICAL METALLIC TUBING (EMT) HAVE DETACHED FROM THE BOTTOM OF THE SERVICE DISCONNECT.

8. THERE ARE EXPOSED FEEDERS AT THE BOTTOM OF THE SERVICE DISCONNECT

9. THERE IS GRAY ELECTRICAL CONDUIT WHICH RUNS FROM THE BOTTOM OF THE SERVICE DISCONNECT AND RUNS ALONG THE SURFACE AROUND THE MOBILE HOME, THE CONDUIT IS NOT PROPERLY SECURED AND PRONE TO PHYSICAL DAMAGE.
10. THE WOOD SUPPORT SYSTEM IS UNSTABLE AND NOT PROPERLY SUPPORTED.

SERVICE DISCONNECT LOCATION FOR UNITS 23 /24 /25
THIS SERVICE IS LOCATED IN SPACE 23

1. INCORRECT GROUNDING ELECTRODE CONDUCTOR


SERVICE DISCONNECT FOR UNIT 26 LOCATED IN SPACE 26

1. VERIFY GROUNDING SYSTEM

2. UNUSED OPENING

MOBILE HOME AND RV UNITS VIOLATIONS ARE LISTED BELOW
UNIT 1
VACANT SPACE
NO DISCONNECT MEANS

UNIT 2
OVER CURRENT PROTECTION IS A 40 AMP MAIN BREAKER
THE MAIN BREAKER AT THE SERVICE IS A 40 AMPS MAIN BREAKER, THE POWER SUPPLY CORD AND DISCONNECTING MEANS RECEPTACLE IS RATED FOR 30 AMPS.. THE OVERCURRENT PROTECTION EXCEEDS THE AMPACITY OF THE CONDUCTORS.
WORKING CLEARING IS OBSTRUCTED
NO GROUNDING ELECTRODE SYSTEM

EXPOSED CONDUCTORS AT THE RECEPTACLE

RECEPTACLE NOT PROPERLY INSTALLED AND UNSECURED TO THE ENCLOSURE

THE RECEPTACLE ENCLOSURE IS NOT PROPERLY SECURED TO THE POST
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

UNIT 3
OVER CURRENT PROTECTION IS A 30 AMP MAIN BREAKER
DISCONNECTING MEANS RECEPTACLE IS 30 AMPS
NO GROUNDING ELECTRODE SYSTEM

EXPOSED CONDUCTORS WHERE THE POWER SUPPLY CORD MEETS THE CORD CAP.
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

UNIT 4
OVER CURRENT PROTECTION IS A 50 AMP MAIN BREAKER
THE MAIN BREAKER AT THE SERVICE IS A 50 AMPS MAIN BREAKER, THE POWER SUPPLY CORD AND DISCONNECTING MEANS RECEPTACLE IS RATED FOR 30 AMPS. THE OVERCURRENT PROTECTION EXCEEDS THE AMPACITY OF THE CONDUCTORS.
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

NO GROUNDING ELECTRODE SYSTEM

THE PVC PIPE IS NOT LISTED FOR ITS USE AS CONDUIT.

THE SUPPORT SYSTEM IS UNSTABLE AND NOT PROPERLY SUPPORTED.


UNIT 5

OVER CURRENT PROTECTION IS A 50 AMP MAIN BREAKER
THE MAIN BREAKER AT THE SERVICE IS A 50 AMPS MAIN BREAKER, THE POWER SUPPLY CORD AND DISCONNECTING MEANS RECEPTACLE IS RATED FOR 30 AMPS. THE OVERCURRENT PROTECTION EXCEEDS THE AMPACITY OF THE CONDUCTORS.
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

NO GROUNDING ELECTRODE SYSTEM

THE SUPPORT SYSTEM IS UNSTABLE AND NOT PROPERLY SUPPORTED.

UNIT 6

OVER CURRENT PROTECTION IS A 30 AMP MAIN BREAKER
DISCONNECTING MEANS RECEPTACLE IS 30 AMPS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

NO GROUNDING ELECTRODE SYSTEM

WORKING CLEARANCE IS OBSTRUCTED
THE SUPPORT SYSTEM IS UNSTABLE AND NOT PROPERLY SUPPORTED.

DEAD FRONT HAS BEEN MODIFIED FOR ADDITIONAL DUPLEX RECEPTACLE.







UNIT 7
OVER CURRENT PROTECTION IS A40 AMP MAIN BREAKER
THE MAIN BREAKER AT THE SERVICE IS A 40 AMPS MAIN BREAKER, THE DISCONNECTING MEANS BREAKER IS RATED FOR 30 AMPS. THE OVERCURRENT PROTECTION EXCEEDS THE AMPACITY OF THE CONDUCTORS.

NO GROUNDING ELECTRODE SYSTEM
UNUSED OPENINGS
THE SUPPORT SYSTEM IS UNSTABLE AND NOT PROPERLY SUPPORTED
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

UNIT 8
OVER CURRENT PROTECTION IS A50 AMP MAIN BREAKER
DISCONNECTING MEANS RECEPTACLE IS 50 AMPS
NO GROUNDING ELECTRODE SYSTEM
THERE ARE TWO UNDERGROUND FEEDER TYPE OF CABLES (GRAY NON SHEATHED METALLIC CABLES) EXPOSED AND ABOVE GROUND BEING USED AS THE POWER SUPPLY CORD. THESE CABLES HAVE BEEN INSTALLED IN A MANNER PRONE TO PHYSICAL DAMAGE. THIS IS AN UNAPPROVED WIRING METHODS.
THE JUNCTION BOX HAS BEEN MODIFIED FOR THE INSTALL OF A 50 AMP RECEPTACLE. THE J BOX HAS A PVC TYPE PLUG ON THE ENCLOSURE.
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

THE SUPPORT SYSTEM IS UNSTABLE AND NOT PROPERLY SUPPORTED

UNIT 9
OVER CURRENT PROTECTION IS A50 AMP MAIN BREAKER
VERIFY DISCONNECTING MEANS FUSE TYPE AND SIZE
NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

THE SUPPORT SYSTEM IS UNSTABLE AND NOT PROPERLY SUPPORTED


UNIT 10
OVER CURRENT PROTECTION IS A50 AMP MAIN BREAKER
THE MAIN BREAKER AT THE SERVICE IS A 50 AMPS MAIN BREAKER, THE DISCONNECTING MEANS IS A FUSE WHICH IS UNREADABLE
DAMAGED DUPLEX RECEPTACLE
NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

VERIFY DISCONNECTING MEANS FUSE TYPE AND SIZE


UNIT 11 D
VACANT SPACE
OVER CURRENT PROTECTION IS A50 AMP MAIN BREAKER
THE MAIN BREAKER AT THE SERVICE IS A 50 AMPS MAIN BREAKER, THE DISCONNECTING MEANS RECEPTACLE IS RATED FOR 30 AMPS. THE OVERCURRENT PROTECTION EXCEEDS THE AMPACITY OF THE CONDUCTORS.

UNUSED OPENING
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

NO GROUNDING ELECTRODE SYSTEM


UNIT 11 B
VACANT SPACE
OVER CURRENT PROTECTION IS A30 AMP MAIN BREAKER
MISSING DISCONNECTING MEANS RECEPTACLE
EXPOSED UNPROTECTED WIRING INSIDE THE ENCLOSURE
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

NO GROUNDING ELECTRODE SYSTEM

UNIT 11 AND 11 C
OVER CURRENT PROTECTION IS A50 AMP MAIN BREAKER
FOR BOTH 11 AND 11C
LAUNDRY ROOM
BUILDING NOT IN USED, BOARDED
MISSING DEAD FRONTS AND COVERS ON THE ELECTRICAL PANELS
EXPOSED WIRING
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

NO GROUNDING ELECTRODE SYSTEM

UNIT 12
OVER CURRENT PROTECTION IS UNREADABLE
DISCONNECTING MEANS RECEPTACLE IS 50 AMPS
NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

UNIT 13
OVER CURRENT PROTECTION IS A45 AMP MAIN BREAKER
DISCONNECTING MEANS RECEPTACLE IS 50 AMPS
NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

THE SUPPORT SYSTEM IS UNSTABLE AND NOT PROPERLY SUPPORTED

UNIT 14
OVER CURRENT PROTECTION IS 40 AMPS
THE MAIN BREAKER AT THE SERVICE IS A 40 AMPS MAIN BREAKER, THE DISCONNECTING MEANS RECEPTACLE IS RATED FOR 50 AMPS. THE OVERCURRENT PROTECTION EXCEEDS THE AMPACITY OF THE CONDUCTORS.

MISSING HARDWARE ON THE ENCLOSURE
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

UNIT 15
OVER CURRENT PROTECTION IS UNREADABLE
DISCONNECTING MEANS RECEPTACLE IS RATED AT 50 AMPS
NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

WORKING CLEARANCE OBSTRUCTION

UNIT 16
OVER CURRENT PROTECTION IS A 30 AMP MAIN BREAKER
THE MAIN BREAKER AT THE SERVICE IS A 30 AMPS MAIN BREAKER, THE DISCONNECTING MEANS RECEPTACLE IS RATED FOR 50 AMPS
MISSING DEAD FRONT
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

NO GROUNDING ELECTRODE SYSTEM
THE SUPPORT SYSTEM IS UNSTABLE AND NOT PROPERLY SUPPORTED

UNIT 17
OVER CURRENT PROTECTION IS UNREADABLE
DISCONNECTING MEANS RECEPTACLE IS RATED FOR 50 AMPS

THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

NO GROUNDING ELECTRODE SYSTEM


UNIT 18
OVER CURRENT PROTECTION IS A 30 AMP BREAKER
DISCONNECTING MEANS RECEPTACLE IS RATED AT 30 AMPS
NO GROUNDING ELECTRODE SYSTEM
UNUSED OPENINGS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

UNIT 19
OVER CURRENT PROTECTION IS 50 AMP BREAKER
HARDWIRED

UNIT 20
200 AMP SERVICE

UNIT 21
OVER CURRENT PROTECTION IS UNREADABLE
DISCONNECTING MEANS RECEPTACLE IS 30 AMPS
NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

UNIT 22
OVER CURRENT PROTECTION IS 50
DISCONNECTING MEANS RECEPTACLE IS RATED FOR 50 AMPS
NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

UNIT 23
OVER CURRENT PROTECTION IS 50 AMP BREAKER
50 AMP HARDWIRED
NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS


UNIT 24
OVER CURRENT PROTECTION IS 50 AMP BREAKER
THE MAIN BREAKER AT THE SERVICE IS A 50 AMPS MAIN BREAKER, THE POWER SUPPLY CORD AND DISCONNECTING MEANS RECEPTACLE IS RATED FOR 30 AMPS. THE OVERCURRENT PROTECTION EXCEEDS THE AMPACITY OF THE CONDUCTORS.
NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

WORKING CLEARANCE OBSTRUCTION BY FENCE

UNIT 25
OVER CURRENT PROTECTION IS 50 AMP BREAKER
THE MAIN BREAKER AT THE SERVICE IS A 50 AMPS MAIN BREAKER, THE POWER SUPPLY CORD AND DISCONNECTING MEANS RECEPTACLE IS RATED FOR 40 AMPS. THE OVERCURRENT PROTECTION EXCEEDS THE AMPACITY OF THE CONDUCTORS.
NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

UNIT 26
VACANT SPACE
100 AMP SERVICE
UNUSED OPENING
VERIFY GROUNDING SYSTEM

UNIT 27
VACANT SPACE
NO EQUIPMENT
09/21/2016 INSP - FOLLOW UP CODE ENFORCE Follow-up inspection ONSITE INSPECTION OF THE PARKS SERVICES, NO MANAGEMENT ONSITE, NORTH DISCONNECTS LOCATED IN SPACE 3 ARE NOT ACCESSIBLE.. TOOK PHOTOS OF THE PARKS SERVICES