Case: T16DV05593

Parcel: 10612016A


Addresses:

1681 W PRINCE RD


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T16DV05593

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
09/12/2016 INSP - INITIAL CODE ENFORCMENT Approved ONSITE INSPECTION OF THE PARK'S ELECTRICAL SERVICE AND EQUIPMENT. THERE IS NO ACCESS TO THE FOLLOWING UNITS 2, 3, 9, 10, 14, 16, 17, 19, 21, 22 AND THE SERVICE LOCATED INSIDE UNIT 3 YARD.

UNIT 1
VACANT SPACE
NO DISCONNECT MEANS
MISSING CLEAN OUT CAP

UNIT 2
NO ACCESS

UNIT 3
NO ACCESS

UNIT 4
30 AMP RECEPTACLE
NO ACCESS TO OVER CURRECT PROTECTION DEVICE, MANAGER ONSITE?
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

NO GROUNDING ELECTRODE SYSTEM

THE CONDUIT IS NOT RATED FOR ITS USE

THE SUPPORT SYSTEM IS UNSTABLE AND NOT PROPERLY SUPPORTED.

UNIT 5

30 AMP RECEPTACLE
NO ACCESS TO OVER CURRECT PROTECTION DEVICE, MANAGER ONSITE?
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

NO GROUNDING ELECTRODE SYSTEM

THE SUPPORT SYSTEM IS UNSTABLE AND NOT PROPERLY SUPPORTED.

UNIT 6

30 AMP RECEPTACLE
NO ACCESS TO OVER CURRECT PROTECTION DEVICE, MANAGER ONSITE?
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

NO GROUNDING ELECTRODE SYSTEM

WORKING CLEARANCE IS OBSTRUCTED
THE SUPPORT SYSTEM IS UNSTABLE AND NOT PROPERLY SUPPORTED.

UNIT 7
30 AMP DISCONNECTING MEANS / WITH BREAKER
NO GROUNDING ELECTRODE SYSTEM
UNUSED OPENINGS
THE SUPPORT SYSTEM IS UNSTABLE AND NOT PROPERLY SUPPORTED

UNIT 8
50 AMP RECEPTACLE
NO ACCESS TO OVER CURRECT PROTECTION DEVICE, MANAGER ONSITE?
NO GROUNDING ELECTRODE SYSTEM
THERE ARE TWO GRAY NON SHEATHED METELLIC CABLES EXPOSED AND ABOVE GROUND BEING USED AS THE POWER SUPPLY CORD. THESE CABLES IN THE MANNER CONNECTED ARE PRONE TO PHYICAL DAMAGE. THIS IS AN UNAPPROVED WIRING METHODS.
THE JUNCTION BOX HAS BEEN MODIFIED FOR THE INSTALL OF A 50 AMP RECEPTACLE. THE J BOX HAS A PVC TYPE PLUG.
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS


UNIT 9
NO ACCESS
UNIT 10
NO ACCESS

UNIT 11 RE INSPECTION REQUIRED
UNIT 11 B
UNIT 11 C

UNIT 12
50 AMP RECEPTACLE
NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

UNIT 13
50 AMP RECEPTACLE
NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

THE SUPPORT SYSTEM IS UNSTABLE AND NOT PROPERLY SUPPORTED

UNIT 14
NO ACCESS

UNIT 15
50 AMP RECEPTACLE
NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

WORKING CLEARANCE OBSTRUCTION

SERVICE LOCATION FOR UNITS 12 / 17
UF CABLE EXPOSED FROM THE DISCONNECT TO THE EARTH, NOT AN APPROVED WIRING METHOD

UNIT 16
NO ACCESS

UNIT 17
NO ACCESS

UNIT 18
30 AMP DISCONNECTING MEANS / WITH BREAKER
NO GROUNDING ELECTRODE SYSTEM
UNUSED OPENINGS

UNIT 19
NO ACCESS

UNIT 20
IS OK, 200 AMP SERVICE

UNIT 21
NO ACCESS

UNIT 22
NO ACCESS

UNIT 23
50 AMP HARDWIRED
NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS


SERVICE LOCATION FOR UNITS 23 /24 /25
ALL 50 AMPS


UNIT 24

30 AMP RECEPTACLE NO OVERCURERENCT PROTECTION, DISCONNECT IS RATED AT 50 AMPS.

POWER SUPPLY CORD IS RATED AT 30 AMPS ( VERIFIY POWER SUPPY CORD AMPERS)

NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS

WORKING CLEARANCE OBSTRUCTION BY FENCE

UNIT 25
40 AMP RECEPTACLE NO OVERCURERENCT PROTECTION, DISCONNECT IS RATED AT 50 AMPS.

POWER SUPPLY CORD IS RATED AT 40 AMPS ( VERIFIY POWER SUPPY CORD AMPERS)

NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS