Case: T16DV04841

Parcel: 107081630


Addresses:

725 W JACINTO ST

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
08/10/2016 INSP - INITIAL CODE ENFORCMENT Approved 08/10/2016 - Compliant: Emergency House Fire:
Arrived on site and met with fire captain and then fire inspector. Fire was in rear bedroom ceiling and wall and ceiling in closet in same room. Wire in old conduit was the point of ignition . Two holes cut in roof & ceiling in bedroom and closet by fire deptment, approx. 3x3. Sheet of sheetrock also rip down in wall, again from fire dept. Roof was tarped by FD. Electrical system had a sub panel in closet of 1st bedroom and fuses did not pop. Checked main panel fire dept states they shut all breakers and breaker did not trip during fire. Panel lacks working space dure to washer and dryer in way. Panel lacks main disconnect. First bedroom lacks egress both windows blocked by window A/C units. Extension cords in first bedroom Southwest Gas checked and pined gas meter.