Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2016 | INSP - INITIAL CODE ENFORCMENT | Approved | Compliant:Electric work without permit last week causing a short and electric shock from the front light switch. Arrived on site with Inspector Hollander TEP already on site, TEP check the box and meter all was fine, Inspector Hollander indentified the system as a two wire system from box. Made contact with tenant states when he touched the light switch to front porch light and front door was shocked. Inspector tested striker plate and got a reading as it being powered when he touches light switch. Eliminated hazzard by removing bottom screw to plate however stiker plate and door was still operational. Checke sub panel in closet to master bedroom all was in order, No smoke detectors in bedrooms or hallway leading to bedrooms. Bedrooms had newer outlets but were 3 wire outlets on a 2 wire system, grounded receptacles on non grounded system in both bedrooms. New outlets again 3 wires in bothroom and kitchen with out being GFCI. Newer gas furnace see in unit without permit, will get with supervision before nov is given out. Again hazzard eleminated before we left the site |