Case: T16DV03450

Parcel: 130050820


Addresses:

1847 S OLSEN AV

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
06/18/2016 INSP - INITIAL CODE ENFORCMENT Approved EMERGENCY CALL-OUT BY TUCSON FIRE:
INSPECTED THE INTERIOR OF THE DWELLING UNIT FOUND GFCI RECEPTACLE IN THE KITCHEN WITH BURN MARKS.
TENANT STATES THAT THERE WAS AN ARC SO SHE CALLED THE FIRE DEPARTMENT, SHE STATES THAT THE ENTIRE ELECTRICAL SYSTEM IN THE HOUSE IS DANGEROUS. I INSPECTED THE INTERIOR OF THE ROOMS AND FOUND OTHER OUTLETS WITH MISSING COVER PLATES AND DAMAGED COVER PLATES.
I DID INSPECTION OF THE MAIN SERVICE WHICH IS A 40 AMP DISCONNECT WITH THREE OTHER 30 AMP FUSE BOXES WHICH HAVE BEEN ADDED OVER TIME. I FOUND A 220V DRYER CONNECTED TO A 110 OUTLET.
THE TENANT AND STATES OF THE DRYER DOESN'T WORK BECAUSE THE FUSES BLOW. THE DWELLING UNIT WAS CONDEMNED DUE TO FAULTY ELECTRICAL AND UNPERMITTED ELECTRICAL WORK INSIDE THE MAIN DISCONNECT AND THE OTHER FUSE BOXES. TERMINAL LUGS ON THE MAIN DISCONNECT AND OTHER FUSE BOXES HAVE MULTIPLE CONDUCTORS.THE DWELLING UNIT WAS CONDEMNED, TEP DID SHUT THE POWER OFF TO THE MAIN DISCONNECT.
SCHEDULE A 30 DAYS FOLLOW UP INSPECTION.